CL-2
-
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
* Some defaults are model number dependent.
ITEM EXPANSION RANGE DEFAULT SETTING
M.PID MOTORMASTER PID CONFIGS
MM.RR Motor Master PI Run Rate 5 to 120 5
MM.PG Motor Master Prop. Gain 0 to 5 1.0
MM.PD Motor Master Deriv. Gain 0 to 5 0.3
MM.TI Motor Master Integ. Time 0.5 to 50 30.0
SCT.H Maximum Condenser Temp 100 to 150 115
SCT.L Minimum Condenser Temp 40 to 90 72
DG.A1 A1 is a Digital Scroll No/Yes No
MC.A1 A1 Min Digital Capacity 30 to 100 50
DS.AP Dig Scroll Adjust Delta 0 to 100 % 100
DS.AD Dig Scroll Adjust Delay 15 to 60 sec 20
DS.RP Dig Scroll Reduce Delta 0 to 100 % 6
DS.RD Dig Scroll Reduce Delay 15 to 60 sec 30
DS.RO Dig Scroll Reduction OAT 70 to 120 dF 95
DS.MO Dig Scroll Max Only OAT 70 to 120 dF 105
MLV Min Load Valve Enable Disable/Enable Disable
H.SST Hi SST Alert Delay Time 5 to 30 min 10
RR.VF Rev Rotation Verified ? No/Yes No
CS.HP Use CSBs for HPS detect? No/Yes Yes
EXV.C EXV CIRCUIT CONFIGS
EX.SA Cir. EXV Start Algorithm 0 to 1 1
SH.SP EXV Superheat Setpoint 5 to 40 12.0
ST.SH Cir. EXV Startup SH SP 1 to 10 3.0
SH.DB EXV Superheat Deadband 0 to 2 0.5
MOP.S Max Oper. Pressure SP 40 to 120 112
CS.DE EXV Cir Start Delay Secs 10 to 240 180
CS.PD EXV Cir PreMove Dly Secs 0 to 30 0
EX.MN Comp. Cir. Exv. Min Pos% 0 to 100 20.0
EX.MC Comp Cir EXV Mn Strt Pos 0 to 100 40.0
E.PID EXV PID CONFIGS
EX.RR EXV PID Run Rate 5 to 120 5
EX.PG EXV PID Prop. Gain 0 to 5 0.15
EX.TI EXV Integration Time 0.5 to 60 12.0
EX.FG %EXV Move on Cir. Stg Up 0 to 100 15.0
EX.FD %EXV Move on Cir. Stg Dw 0 to 100 15.0
EX.CF EXV Pre-Move Config 0 to 3 1
EX.PM EXV Pre-Move Delay Secs 0 to 30 10
FL.SP EXV SH Flooding Setpoint 0 to 10 6.0
FL.OV Flooding Override Pct. -10 to -1 -4.0
FL.OC Flood Ovrde Press Cutoff 0 to 1000 600.0
FL.OD Flooding Override Delay 0 to 255 0
EX.SL EXV Init Pos Slope -100 to 100 -1.0
EX.IN EXV Init Pos Intercept -200 to 200 110.0
EX.HO Hmzr Oil Ret Flood Ovrde 0 to 2 0
EX.SM EXV Smoothing Algorithm 0 to 1 1
DP.OC DP OVERRIDE CONFIGS
DP.RS DP Rate of Change Set 2 to 15 10
DP.RC DP Rate of Change Clr 0 to 5 1
DP.L1 DP Override Limit 1 400 to 450 400
DP.L2 DP Override Limit 2 480 to 550 500
DP.TO DP Override Timeout 6 to 150 90
DP.OR DP Override Percent 0 to 15 10
EDT.R EVAP.DISCHRGE TEMP RESET
RS.CF EDT Reset Configuration 0 to 3 (multi-text strings) 2
RTIO Reset Ratio 0 to 10 2
LIMT Reset Limit 0 to 20 ^F 10
RES.S EDT 4-20 ma Reset Input Disable/Enable Disable
HEAT HEATING CONFIGURATION
HT.CF Heating Control Type 0 to 5 0*
HT.SP Heating Supply Air Setpt 65 to 120 dF 85
OC.EN Occupied Heating Enabled No/Yes No
LAT.M MBB Sensor Heat Relocate No/Yes No
SG.CF STAGED HEAT CONFIGS
HT.ST Modulating Gas Type 0 to 3 0*
CAP.M Max Cap Change per Cycle 5 to 45 45*
M.R.DB St.Ht DB min.dF/PID Rate 0 to 5 0.5
S.G.DB St.Heat Temp. Dead Band 0 to 5 ^F 2
RISE Heat Rise dF/sec Clamp 0.05 to 0.2 0.06
LAT.L LAT Limit Config 0 to 20 ^F 10
LIM.M Limit Switch Monitoring? No/Yes Yes
SW.H.T Limit Switch High Temp 80 to 210 dF 170*
SW.L.T Limit Switch Low Temp 80 to 210 dF 160*
HT.P Heat Control Prop. Gain 0 to 1.5 1
HT.D Heat Control Derv. Gain 0 to 1.5 1
HT.TM Heat PID Rate Config 30 to 300 sec 90