CONTROLS SET POINT AND CONFIGURATION LOG (cont)
ITEM EXPANSION RANGE DEFAULT SETTING
ECON (CONT)
T.24.C TITLE 24 CONFIGS
T.24.CLOG.F Log Title 24 Faults Yes/No No
T.24.CEC.MD T24 Econ Move Detect 1 - 10 1
T.24.CEC.ST T24 Econ Move SAT Test 10 - 20 10
T.24.CS.CHG T24 Econ Move SAT Change 0 - 5 0.2
T.24.CE.SOD T24 Econ RAT-OAT Diff 5 - 20 15
T.24.CE.CHD T24 Heat/Cool End Delay 0 - 60 25
T.24.CET.MN T24 Test Minimum Pos. 0 - 50 15
T.24.CET.MX T24 Test Maximum Pos. 50 - 100 85
T.24.CSAT.T SAT Settling Time 10 - 900 240
T.24.CAC.EC Economizer Deadband Temp 0 - 10 4
T.24.CE.GAP Econ Fault Detect Gap 2 - 100 5
T.24.CE.TMR Econ Fault Detect Timer 10 - 240 20
T.24.CX.CFM Excess Air CFM 400 - 4000 800
T.24.CX.TMR Excess Air Detect Timer 30 - 240 150
T.24.CAC.MR T24 AutoTest SF Run Time 1 - 10 2
T.24.CAC.SP T24 Auto-Test VFD Speed 10 - 50 20
T.24.CAC.OP T24 Auto-Test Econ % Opn 1 - 100 30
T.24.CVF.PC T24 Auto-Test VFD % Chng 1 - 20 10
T.24.CEC.DY T24 Econ Auto-Test Day 0=Never, 1=Monday, 2=Tuesday,
3=Wednesday, 4=Thursday, 5=Friday,
6=Saturday, 7=Sunday
6=Saturday
T.24.CEC.TM T24 Econ Auto-Test Time 0 - 23 2
BP BUILDING PRESS. CONFIGS
BP.CF Building Press. Config 0 to 2 0*
BP.S Building Pressure Sensor Disable/Enable Disable*
BP.R Bldg. Press. (+/-) Range 0.1 to 0.25 "H2O 0.25
BP.SP Building Pressure Setp. -0.25 to 0.25 "H2O 0.05
BP.SO BP Setpoint Offset 0 to 0.5 "H2O 0.05
B.V.A VFD/ACTUATOR CONFIG
B.V.ABP.FS VFD Fire Speed 0 to 100 % 100
B.V.ABP.MN VFD Minimum Speed 0 to 100 % 10
B.V.ABP.MX VFD Maximum Speed 0 to 100 % 100
FAN.T FAN TRACKING CONFIG
FAN.TFT.CF Fan Track Learn Enable No/Yes No
FAN.TFT.TM Fan Track Learn Rate 5 to 60 min 15
FAN.TFT.ST Fan Track Initial DCFM -20000 to 20000 cfm 2000
FAN.TFT.MX Fan Track Max Clamp 0 to 20000 cfm 4000
FAN.TFT.AD Fan Track Max Correction 0 to 20000 cfm 1000
FAN.TFT.OF Fan Track Internl EEPROM -20000 to 20000 cfm 0
FAN.TFT.RM Fan Track Internal RAM -20000 to 20000 cfm 0
FAN.TFT.RS Fan Track Reset Internal No/Yes No
FAN.C SUPPLY, RET/EXH FAN CFG
FAN.CSCF.C Supply Air CFM Config 1 to 2 (multi-text strings) 2
FAN.CREF.C Ret/Exh Air CFM Config 1 to 2 2
FAN.C
SCF.S Supply Air CFM Sensor Disable/Enable Disable*
FAN.CRCF.S Return Air CFM Sensor Disable/Enable Disable*
FAN.CECF.S Exhaust Air CFM Sensor Disable/Enable Disable*
B.PID BLDG.PRESS.PID CONFIGS
B.PIDBP.TM Bldg.Pres.PID Run Rate 1 to 60 sec 10
B.PIDBP.P Bldg.Press. Prop. Gain 0 to 5 0.5
B.PIDBP.I Bldg.Press. Integ. Gain 0 to 2 0.5
B.PIDBP.D Bldg.Press. Deriv. Gain 0 to 5 0.3
D.LV.T COOL/HEAT SETPT. OFFSETS
D.LV.TL.H.ON Dmd Level Lo Heat ON 0 to 2 ^F 1.5
D.LV.TH.H.ON Dmd Level(+) Hi Heat ON 0.5 to 20 ^F 0.5
D.LV.TL.H.OF Dmd Level(-) Lo Heat OFF 0.5 to 2 ^F 1
D.LV.TL.C.ON Dmd Level Lo Cool ON 0 to 2 ^F 1.5
D.LV.TH.C.ON Dmd Level(+) Hi Cool ON 0.5 to 20 ^F 0.5
D.LV.TL.C.OF Dmd Level(-) Lo Cool OFF 0.5 to 2 ^F 1
D.LV.TC.T.LV Cool Trend Demand Level 0.1 to 5 ^F 0.1
D.LV.TH.T.LV Heat Trend Demand Level 0.1 to 5 ^F 0.1
D.LV.TC.T.TM Cool Trend Time 30 to 600 sec 120
D.LV.TH.T.TM Heat Trend Time 30 to 600 sec 120