EasyManua.ls Logo

Carrier WeatherExpert 48N2 - Page 45

Carrier WeatherExpert 48N2
248 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
45
Configuration
SP
SP.RS = 1 (Static Pressure Reset us-
ing 4-20ma sensor)
Configuration
SP
SP.RS = 4 (Static Pressure Reset us-
ing VFD Control)
Configuration
ECON
CFM.C
OCF.S = Enable (Out-
door Air CFM Sensor Enable)
Configuration
EDT.R
RES.S = Enable (4-20 ma Sup-
ply Air Reset Sensor Enable)
Configuration
ECON
ORH.S = Enable (Outside Air
Relative Humidity Sensor Enable)
Configuration
IAQ
DEHU
D.SEN = 3 (DISCR.IN-
PUT) (Dehumidification Sensor - Discrete Input Select)
Configuration
BP
DMD.L
DM.L.S = 1 (2 SWITCH-
ES) (Demand Limiting using 2 discrete switches)
Configuration
BP
DMD.L
DM.L.S = 2 (4-20MA
CTRL) (Demand Limiting using a 4-0ma sensor)
Configuration
IAQ
AQ.CF
IQ.I.C = 1 (IAQ DIS-
CRETE) (IAQ discrete switch control)
Configuration
IAQ
AQ.CF
IQ.I.C = 2 (IAQ
DISC.OVR) (IAQ discrete switch "override" control)
Configuration
IAQ
AQ.CF
OQ.A.C = 1 (OAQ
SENS-DAQ) (Outdoor Air Quality Sensor)
Configuration
IAQ
AQ.CF
OQ.A.C = 2 (4-20 NO
DAQ) (4-20ma sensor, no DAQ)
Configuration
IAQ
FLTC
MFL.S = 1,3,4,5 (Main
Filter Status is not disabled or schedule)
Configuration
IAQ
FLTC
PFL.S = 1,3,4,5 (Post Fil-
ter Status is not disabled or schedule)
Liquid Sensors Installed (
LQ.SN) — This configuration in-
structs the control to read the liquid temperature thermistors
and pressure transducers on A and B refrigeration circuits.
Power Monitor Installed (
PW.MN) — This configuration in-
structs the control to monitor the power status input.
VFD Bypass Enable (
VFD.B) — This configuration instructs
the control to enable the EXB in order to use the supply fan re-
lay (SFBYRLY) and ret/exh bypass relay (PEBRLY) outputs.
UV-C Lamp Configuration (
UVC.L) — This configuration
controls the enabling of the UV-C lamps to 0) none, 1) enabled,
2) enabled with status feedback.
Temperature Compensation Start Cooling Factor (
TCS.C
)
— This factor is used in the equation of the Temperature Com-
pensated Start Time Bias for cooling. Refer to the Temperature
Compensated Start section for more information. A setting of
0 minutes indicates Temperature Compensated Start in Cool-
ing is not permitted.
Temperature Compensated Start Heating Factor (
TSC.H
)
— This factor is used in the equation of the Temperature Com-
pensated Start Time Bias for heating. Refer to the Temperature
Compensated Start section for more information. A setting of
0 minutes indicates Temperature Compensated Start in Heating
is not permitted.
Fan Fail Shuts Down Unit (
SFS.S) — This configuration
will allow whether the unit should shut down on a supply fan
status fail or simply alert the condition and continue to run.
YES – Shut down the unit if supply fan status monitoring fails
and send out an alarm
NO – Do not shut down the unit if supply fan status monitor-
ing fails but send out an alert.
Fan Status Monitoring Type (
SFS.M) — This configuration
selects the type of fan status monitoring to be performed.
0 – NONE – No switch or monitoring
1 – SWITCH – Use of the fan status switch
2 – SP RISE – Monitoring of the supply duct pressure.
VAV Unoccupied Fan Retry Time (
VAV.S) — Machine con-
trol types 1 and 2 (VAV-RAT,VAV-SPT) include a process for
sampling the return-air temperature during unoccupied periods
to prove a valid demand for heating or cooling before initiating
an unoccupied heating or cooling mode. If the sampling rou-
tine runs but concludes a valid demand condition does not ex-
ist, the sampling process will not be permitted for the period of
time defined by this configuration. Reducing this value allows
a more frequent re-sampling process. Setting this value to zero
will prevent any sampling sequence.
MAT Calc Config (
MAT.S) — This configuration gives the
user three options in the processing of the mixed-air tempera-
ture (MAT) calculation:
MAT.S = 0
The control will not attempt to learn MAT over time. The
control will simply calculate MAT based on the position
of the economizer, outside and return air temperature,
linearly.
MAT.S = 1
The control will attempt to learn MAT over time. Any
time the system is in a vent mode and the economizer
stays at a particular position for long enough, MAT =
EDT. Using this, the control has an internal table
whereby he can more closely zoom in on the true MAT
value.
MAT.S = 2
The control will stop learning and use whatever the con-
trol has already learned. This would infer that the control
spent a part of its life at MAT.S = 1. This might be useful
to a commissioner of a system who first sets MAT.S = 1,
then might go into the service test mode, turn on the fan
and open the economizer to a static position for a little
more than 5 minutes and then move to several positions
to repeat the same (20%,40%,60%,80%). The only stipu-
lation to this "commissioning" is that it is important that
the difference between return and outside temperature be
greater than 5 degrees. (The greater the delta, the better.)
When done, set MAT.S = 2 and the system has been
"learned" forever.
Reset MAT Table Entries? (
MAT.R) — This configuration
allows the user to reset the internally stored MAT "learned"
configuration entities back to their default values. The defaults
are set to a linear relationship between the economizer damper
position and OAT and RAT in the calculation of MAT.
Altitude.......in feet: (
ALTI) — As the control does not in-
clude a barometric pressure sensor to thoroughly define the cal-
culation of enthalpy and CFM, the control does include an alti-
tude parameter which will serve to set up a "mean" barometric
pressure for use to calculate with. The effect of barometric
pressure in these calculations is not great, but could have an ef-
fect depending on the installed elevation of the unit. Basically,
if the rooftop is installed at a particularly high altitude and en-
thalpy or CFM are being calculated, set this configuration to
the current elevation of the installed rooftop.
Start Up Delay Time (
DLAY) — This option inhibits the unit
from operating after a power reset. The configuration may be
adjusted from 0 to 900 seconds of delay.
Auxiliary Relay Output Configuration (
AUX.R) — This
configuration allows the user to configure the function of the
auxiliary relay output. The output is 1.4 vac, 5 va maximum.
The configuration can be set from 0 to 3. If AUX.R is set to 0,
the auxiliary relay contact will be energized during an alarm.
The output can be used to turn on an indicator light or sound an
alarm in a mechanical room. If AUX.R is set to 1, the auxiliary
relay will energize when the controls determine dehumidifica-
tion/reheat is needed. The relay would be wired to a third party
dehumidification/reheat device and would energize the device
when needed. If AUX.R is set to 2, the auxiliary relay will ener-
gize when the unit is in the occupied state. The relay could then
be used to control lighting or other functions that need to be on

Table of Contents

Other manuals for Carrier WeatherExpert 48N2

Related product manuals