Circuit B
Coils
120 Ton Standard Efficiency (identical to 75 Ton High Efficiency)
Contactor OFM(s)
Software Board Conrolled Controlled
A CONDFAN1 MBB Rly 6 OFC1 OFM2
B CONDFAN2 MBB Rly 5 OFC2 OFM5
Common CONDFAN3 RCB Rly 1 OFC3 OFM1,6
Common CONDFAN4 RCB Rly 2 OFC4 OFM3,4
# of Fans ON
Fans ON # of Fans ON Fans ON
Stage 1 OFC1 1 OFM2 Stage 1 OFC2 1 OFM5
Stage 2 OFC1,3 2 OFM1,2,6 Stage 2 OFC2,3 2 OFM1,5,6
Circuit A Stage 3 OFC1,3,4 3 OFM1,2,3,4,6 Stage 3 OFC2,3,4 3 OFM1,3,4,5,6
Coils
Low Ambient Prestart 1 (OAT ≤ 50 F) = Stage 1
Low Ambient Prestart 2 (50 F < OAT < 70 F) = Stage 2
High Ambient Prestart (OAT ≥ 70 F) = Stage 3
High Saturated Condensing Temp (SCT>130) = Stage 3
Stage down allowed if SCT<SCT_MIN
Stage up allowed if SCT_MAX<SCT<130
Circuit B
Current stage if SCT_MIN<SCT<SCT_MAX
Coils
130 Ton Standard Efficiency
120-130 Ton High Efficiency (identical to 150 Ton Standard Efficiency)
Contactor OFM(s)
Software Board Conrolled Controlled
A CONDFAN1 MBB Rly 6 OFC1 OFM2
Common CONDFAN2 MBB Rly 5 OFC2 OFM5
B CONDFAN3 RCB Rly 1 OFC3 OFM8
Common CONDFAN4 RCB Rly 2 OFC4 OFM3,7
Common CONDFAN5 RCB Rly 3 OFC5 OFM1,4,6,9
Circuit A
Coils