176
APPENDIX B — CCN TABLES (cont)
MAINTENANCE DISPLAY TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
SUMZ
Cooling Control Point dF COOLCPNT
Mixed Air Temperature dF MAT
Evaporator Discharge Tmp dF EDT
Return Air Temperature dF RAT
Outside Air Temperature dF OAT
Econo Damper Current Pos % ECONOPOS
Capacity Threshold Adjst Z_GAIN
Capacity Load Factor SMZ
Next Stage EDT Decrease ADDRISE
Next Stage EDT Increase SUBRISE
Rise Per Percent Capacity RISE_PCT
Cap Deadband Subtracting Y_MINUS
Cap Deadband Adding Y_PLUS
Cap Threshold Subtracting Z_MINUS
Cap Threshold Adding Z_PLUS
High Temp Cap Override On/Off HI_TEMP
Low Temp Cap Override On/Off LOW_TEMP
Pull Down Cap Override On/Off PULLDOWN
Slow Change Cap Override On/Off SLO_CHNG
SYSTEM
Reset All Current Alarms Yes/No ALRESET config
Reset the Device Yes/No RESETDEV config
Local Machine Disable Yes/No UNITSTOP config
Soft Stop Request Yes/No SOFTSTOP forcible
Emergency Stop Enable/Disable EMSTOP forcible
CEM AN1 10K temp J5,1-2 -40 to 240 dF CEM10K1 forcible
CEM AN2 10K temp J5,3-4 -40 to 240 dF CEM10K2 forcible
CEM AN3 10K temp J5,5-6 -40 to 240 dF CEM10K3 forcible
CEM AN4 10K temp J5,7-8 -40 to 240 dF CEM10K4 forcible
CEM AN1 4-20 ma J5,1-2 0 to 20 ma CEM4201 forcible
CEM AN2 4-20 ma J5,3-4 0 to 20 ma CEM4202 forcible
CEM AN3 4-20 ma J5,5-6 0 to 20 ma CEM4203 forcible
CEM AN4 4-20 ma J5,7-8 0 to 20 ma CEM4204 forcible
TESTCOOL
Compressor A1 Relay ON/OFF CMPA1TST test
Compressor A2 Relay ON/OFF CMPA2TST test
Min. Load Valve (HGBP) ON/OFF MLV_TST test
Compressor B1 Relay ON/OFF CMPB1TST test
Compressor B2 Relay ON/OFF CMPB2TST test
Digital Scroll Capacity 0 to 100 % DSCAPTST test
Humidimizer 3-Way Valve ON/OFF RHVC_TST test
Condenser EXV Position 0 to 100 % CEXVCTST test
Bypass EXV Position 0 to 100 % BEXVCTST test
TESTFANS
Supply Fan Relay ON/OFF SFAN_TST test
Supply Fan VFD Speed 0.0 to 100 % SFVFDTST test
Exhaust Fan VFD Speed 0.0 to 100 % EFVFDTST test
MtrMaster A Commanded % 0.0 to 100 % OAVFDTST test
MtrMaster B Commanded % 0.0 to 100 % OBVFDTST test
Condenser Fan Circuit A ON/OFF CNDA_TST test
Condenser Fan Circuit B ON/OFF CNDB_TST test
Outdoor VFD A Ctrl CMD% 0 to 100 % OV_A_TST test
Outdoor VFD B Ctrl CMD% 0 to 100 % OV_B_TST test
MotorMastr Fan Circuit A ON/OFF MM_A_TST test
MotorMastr Fan Circuit B ON/OFF MM_B_TST test
TESTHEAT
Requested Heat Stage 0 to MAX HTST_TST test
Heat Relay 1 ON/OFF HS1_TST test
Heat Relay 2 ON/OFF HS2_TST test
Relay 3 W1 Gas Valve 2 ON/OFF HS3_TST test
Relay 4 W2 Gas Valve 2 ON/OFF HS4_TST test
Relay 5 W1 Gas Valve 3 ON/OFF HS5_TST test
Relay 6 W2 Gas Valve 3 ON/OFF HS6_TST test
TESTHMZR
Humidimizer 3-Way Valve ON/OFF RHVC_TST
Condenser EXV Position 0 to 100 % CEXVCTST
Bypass EXV Position 0 to 100 % BEXVCTST
Condenser EXV Calibrate ON/OFF CEXV_CAL
Bypass EXV Calibrate ON/OFF BEXV_CAL