APPENDIX A -- LOCAL DISPLAY TABLES (cont)
MODE -- PRESSURES
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS
AIR.P AIR PRESSURES
-*SP Static Pressure "H20 SP
-*BP Building Pressure "H20 BP
REF.P REFRIGERANT PRESSURES
-*DP.A Cir A Discharge Pressure PSIG DPA
-*SP.A Cir A Suction Pressure PSIG SPA
-,DAB Cir B Discharge Pressure PSIG DPB
-,SP.B Cir B Suction Pressure PSIG SPB
MODE -- SET POINTS
DEFAULTITEM
OHSP
OCSP
UHSP
UCSP
GAP
VC.ON
VC.OF
SASP
SA.HI
SA.LO
SA.HT
T.PRG
T.CL
T.VOC
T.VUN
DESCRIPTION
Occupied Heat Setpoint
Occupied Cool Setpoint
Unoccupied Heat Setpoint
Unoccupied Cool Setpoint
Heat-Cool Setpoint Gap
VAV Occ. Cool On Delta
VAV Occ. Cool Off Delta
Supply Air Setpoint
Supply Air Setpoint Hi
Supply Air Setpoint Lo
Heating Supply Air Setpt
Tempering Purge SASP
Tempering in Cool SASP
Tempering Vent Occ SASP
Tempering Vent Unocc. SASP
RANGE
40 -99
40 -99
40 -99
40 -99
2-10
0-25
1-25
45-75
45 -75
45 -75
80-120
-20-80
5-75
-20-80
-20-80
UNITS
dF
dF
dF
dF
deltaF
deltaF
deltaF
dF
dF
dF
dF
dF
dF
dF
dF
CCN POINT
OHSP
OCSP
UHSP
UCSP
HCSP GAP
VAVOCON
VAVOCOFF
SASP
SASP HI
SASP LO
SASPHEAT
TEMPPURG
TEMPCOOL
TEMPVOCC
TEMPVUNC
68
75
55
90
5
3.5
2
55
55
60
85
50
5
65
50
MODE -- INPUTS
ITEM
GEN.I
-,FLT.S
-,G.FAN
-,REMT
-,E.SW
-, E. ENA
-,E.OVR
-,S.FN.S
-,DL.S1
-,DL.S2
-,DH.IN
FD.BK
-,CS.A 1
-,CS.A2
-,CS.B1
-,CS.B2
STAT
-,G
-,W1
-, W2
-,Y1
-, Y2
FIRE
-,FSD
-,PRES
-,EVAC
-,PURG
RELH
-,OA.RH
-,OA.EN
-,OA.DP
-,RA.RH
-,RA.EN
AIR.Q
-,IAQ.I
-,IAQ
-,OAQ
-,DAQ
-,IQ.R O
RSET
-,SA.S.R
-,SP.RS
EXPANSION
GENERAL INPUTS
Filter Status Input
Fan Request From IGC
Remote Input State
Economizer Control Input
Remote Economizer Enable
Econo Position Override
Supply Fan Status Switch
Demand Limit Switch 1
Demand Limit Switch 2
Dehumidify Switch Input
COMPRESSOR FEEDBACK
Compressor A1 Feedback
Compressor A2 Feedback
Compressor B1 Feedback
Compressor B2 Feedback
THERMOSTAT INPUTS
Thermostat G Input
Thermostat W1 Input
Thermostat W2 Input
Thermostat Y1 Input
Thermostat Y2 Input
FIRE-SMOKE INPUTS
Fire Shutdown Input
Pressurization Input
Evacuation Input
Smoke Purge Input
RELATIVE HUMIDITY
Outside Air Rel. Humidity
Outdoor Air Enthalpy
OutsideAir Dewpoint Temp
Return Air Rel. Humidity
Return Air Enthalpy
AIR QUALITY SENSORS
IAQ - Discrete Input
IAQ - PPM Return C02
OAQ - PPM Return C02
Diff.Air Quality in PPM
IAQ Min.Pos. Override
RESET INPUTS
Supply Air Setpnt. Reset
Static Pressure Reset
RANGE
DRTY/C LN
ON/OFF
YES/NO
YES/NO
YES/NO
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ALARM/NORMAL
ALARM/NORMAL
ALARM/NORMAL
ALARM/NORMAL
HIGH/LOW
UNITS
%
dF
%
%
AF
CCN POINT
FLTS
IGCFAN
RMTIN
ECOSW
ECONENBL
ECOORIDE
SFS
DMD SWl
DMD SW2
DHD/SCIN
CSBA1
CSBA2
CSBB1
CSB_B2
G
W1
W2
Y1
Y2
FSD
PRES
EVAC
PURG
OARH
OAE
OADEWTMP
RARH
RAE
IAQIN
IAQ
OAQ
DAQ
IAQMINOV
SASPRSET
SPRESET
WRITE STATUS
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
*The display text changes depending on the remote switch configuration (Configuration-_UNIT-_RM.CF). If RM.CF is set to 0 (No Remote
Switch), then the display text will be "On" or "Off." If RM.CF is set to 1 (Occupied/Unoccupied Switch), then the display text will be "Occupied" or
"Unoccupied." If RM.CFis set to 2 (Start/Stop), then the display text will be "Stop" or "Start." If RM.CFis set to 3 (Override Switch), then the display
text will be "No Override" or "Override."
142