EasyManua.ls Logo

Carrier WEATHERMAKER 48J - Page 173

Carrier WEATHERMAKER 48J
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MODEL NUMBER:
SERIAL NUMBER:
DATE:
TECHNICIAN:
CONTROLS SET POINT AND CONFIGURATION LOG
Software Version
MBB CESR131343--
RCB CESR131249--
ECB CESR131249--
NAVI CESR131227--
SCB CESR131226--
CEM CESR131174--
MARQ CESR131171--
ITEM EXPANSION RANGE DEFAULT ENTRY
UNIT UNIT CONFIGURATION
-_C.TYP Machine Control Type 1 - 6 (multi-text strings) 4
-_CV.FN Fan Mode (O=Auto, l=Cont) 0 - 1 (multi-text strings) 1
-_RM.CF Remote Switch Config 0 -3 (multi-text strings) 0
-_CEM CEM Module Installed Yes/No No
-_TCS.C Temp.Cmp.Strt.Cool Factr 0 - 60 min 0
-_TCS.H Temp.Cmp.Strt.Heat Factr 0 - 60 min 0
-_SFS.S Fan Fail Shuts Down Unit Yes/No No
-_SFS.M Fan Stat Monitoring Type 0 - 2 (multi-text strings) 0
-_VAV.S VAV Unocc.Fan Retry Time 0 - 720 min 50
-_SlZE Unit Size (20-60) 20 - 60 20
-_DP.XR Disch.Press. Transducers Yes/No No
-_SP.XR Suct. Pres. Trans. Type 0 -1 (multi-text strings) 0
-_RFG.T Refrig: 0=R22 1=R410A 0 -1 (multi-text strings) 1
-_CND.T Cnd HX Typ:O=RTPF I=MCHX 0 -1 (multi-text strings) 0
-_MAT.S MAT Calc Config 0 - 2 (multi-text strings) 1
-_MAT.R Reset MAT Table Entries? Yes/No No
-_MAT.D MAT Outside Air Default 0-100% 20
-_ALTI Altitude ........ in feet: 0 - 60000 0
-_DLAY Startup Delay Time 0 - 900 sec 0
-_STAT TSTAT_Both Heat and Cool Yes/No No
-_AUX.R Auxiliary Relay Config 0 - 3 0
-_SENS INPUT SENSOR CONFIG
-_SENS-_SPT.S Space Temp Sensor Enable/Disable Disable
-_SENS-_SP.O.S Space Temp Offset Sensor Enable/Disable Disable
-_SENS-_SP.O.R Space Temp Offset Range 1 - 10 5
-_SENS-_RRH.S Return Air RH Sensor Enable/Disable Disable
-_SENS-_FLT.S Filter Stat.Sw.Enabled ? Enable/Disable Disable
COOL COOLING CONFIGURATION
-_Z.GN Capacity Threshold Adjst -10 - 10 1
-_MC.LO Compressor Lockout Temp -20 - 55 dF 40
-_C.FOD Fan-Off Delay, Mech Cool 0 - 600 sec 60
-_MLV Min. Load Valve? (HGBP) Yes/No No
-_M.M. Motor Master Control Yes/No No
-_HPSP Head Pressure Setpoint 80 - 150 dF 113
-_A I.EN Enable Compressor A1 Enable/Disable Enable
-_A2.EN Enable Compressor A2 Enable/Disable Enable
-_BI.EN Enable Compressor B1 Enable/Disable Enable
-_B2.EN Enable Compressor B2 Enable/Disable Enable
-_CS.A I CSB A1 Feedback Alarm Enable/Disable Enable
-_CS.A2 CSB A2 Feedback Alarm Enable/Disable Enable
-_CS.BI CSB B1 Feedback Alarm Enable/Disable Enable
-_CS.B2 CSB B2 Feedback Alarm Enable/Disable Enable
-_REV.R Rev Rotation Verified ? Yes/No No
-_H.SST Hi SST Alert DelayTime 5 - 30 min 10
EDT.R EVARDISCHRGE TEMP RESET
-_RS.CF EDT Reset Configuration 0 - 3 (multi-text strings) 0
-_RTIO Reset Ratio 0 - 10 2
-_LIMT Reset Limit 0 - 20 ^F 10
-_RES.S EDT 4-20 ma Reset Input Enable/Disable Disable
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53480050-01 Printed in U.S.A. Form 48/50A-7T Pg CL-1 5-08 Replaces: 48/50A-6T

Table of Contents

Related product manuals