MODEL NUMBER:
SERIAL NUMBER:
DATE:
TECHNICIAN:
CONTROLS SET POINT AND CONFIGURATION LOG
Software Version
MBB CESR131343--
RCB CESR131249--
ECB CESR131249--
NAVI CESR131227--
SCB CESR131226--
CEM CESR131174--
MARQ CESR131171--
ITEM EXPANSION RANGE DEFAULT ENTRY
UNIT UNIT CONFIGURATION
-_C.TYP Machine Control Type 1 - 6 (multi-text strings) 4
-_CV.FN Fan Mode (O=Auto, l=Cont) 0 - 1 (multi-text strings) 1
-_RM.CF Remote Switch Config 0 -3 (multi-text strings) 0
-_CEM CEM Module Installed Yes/No No
-_TCS.C Temp.Cmp.Strt.Cool Factr 0 - 60 min 0
-_TCS.H Temp.Cmp.Strt.Heat Factr 0 - 60 min 0
-_SFS.S Fan Fail Shuts Down Unit Yes/No No
-_SFS.M Fan Stat Monitoring Type 0 - 2 (multi-text strings) 0
-_VAV.S VAV Unocc.Fan Retry Time 0 - 720 min 50
-_SlZE Unit Size (20-60) 20 - 60 20
-_DP.XR Disch.Press. Transducers Yes/No No
-_SP.XR Suct. Pres. Trans. Type 0 -1 (multi-text strings) 0
-_RFG.T Refrig: 0=R22 1=R410A 0 -1 (multi-text strings) 1
-_CND.T Cnd HX Typ:O=RTPF I=MCHX 0 -1 (multi-text strings) 0
-_MAT.S MAT Calc Config 0 - 2 (multi-text strings) 1
-_MAT.R Reset MAT Table Entries? Yes/No No
-_MAT.D MAT Outside Air Default 0-100% 20
-_ALTI Altitude ........ in feet: 0 - 60000 0
-_DLAY Startup Delay Time 0 - 900 sec 0
-_STAT TSTAT_Both Heat and Cool Yes/No No
-_AUX.R Auxiliary Relay Config 0 - 3 0
-_SENS INPUT SENSOR CONFIG
-_SENS-_SPT.S Space Temp Sensor Enable/Disable Disable
-_SENS-_SP.O.S Space Temp Offset Sensor Enable/Disable Disable
-_SENS-_SP.O.R Space Temp Offset Range 1 - 10 5
-_SENS-_RRH.S Return Air RH Sensor Enable/Disable Disable
-_SENS-_FLT.S Filter Stat.Sw.Enabled ? Enable/Disable Disable
COOL COOLING CONFIGURATION
-_Z.GN Capacity Threshold Adjst -10 - 10 1
-_MC.LO Compressor Lockout Temp -20 - 55 dF 40
-_C.FOD Fan-Off Delay, Mech Cool 0 - 600 sec 60
-_MLV Min. Load Valve? (HGBP) Yes/No No
-_M.M. Motor Master Control Yes/No No
-_HPSP Head Pressure Setpoint 80 - 150 dF 113
-_A I.EN Enable Compressor A1 Enable/Disable Enable
-_A2.EN Enable Compressor A2 Enable/Disable Enable
-_BI.EN Enable Compressor B1 Enable/Disable Enable
-_B2.EN Enable Compressor B2 Enable/Disable Enable
-_CS.A I CSB A1 Feedback Alarm Enable/Disable Enable
-_CS.A2 CSB A2 Feedback Alarm Enable/Disable Enable
-_CS.BI CSB B1 Feedback Alarm Enable/Disable Enable
-_CS.B2 CSB B2 Feedback Alarm Enable/Disable Enable
-_REV.R Rev Rotation Verified ? Yes/No No
-_H.SST Hi SST Alert DelayTime 5 - 30 min 10
EDT.R EVARDISCHRGE TEMP RESET
-_RS.CF EDT Reset Configuration 0 - 3 (multi-text strings) 0
-_RTIO Reset Ratio 0 - 10 2
-_LIMT Reset Limit 0 - 20 ^F 10
-_RES.S EDT 4-20 ma Reset Input Enable/Disable Disable
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53480050-01 Printed in U.S.A. Form 48/50A-7T Pg CL-1 5-08 Replaces: 48/50A-6T