ITEM EXPANSION RANGE DEFAULT ENTRY
HEAT HEATING CONFIGURATION
-_HT.CF Heating Control Type 0 - 4 0
-_HT.SP Heating Supply Air Setpt 80 - 120 dF 85
-,OC.EN Occupied Heating Enabled Yes/No No
-_LAT.M MBB Sensor Heat Relocate Yes/No No
-,G.FOD Fan-Off Delay, Gas Heat 45-600 45
-_E.FOD Fan-Off Delay, Elec Heat 10-600 30
-_SG.CF STAGED GAS CONFIGS
-_SG.CF-,HT.ST Staged Gas Heat Type 0 - 4 0
-_SG.CF-,CAP.M Max Cap Change per Cycle 5 - 45 45
-_SG.CF-,M.R.DB S,Gas DB min,dF/PID Rate 0 - 5 0,5
-_SG.CF-,S.G.DB St,Gas Temp, Dead Band 0 - 5 ^F 2
-_SG.CF-,RISE Heat Rise dF/sec Clamp 0,05 - 0,2 0,06
-_SG.CF-,LAT.L LAT Limit Config 0 - 20 ^F 10
-_SG.CF-,LIM.M Limit Switch Monitoring? Yes/No No
-_SG.CF-,SW.H.T Limit Switch High Temp 110 - 180 dF 170
-_SG. CF-,SW.L. T Limit Switch Low Temp 1O0 - 170 dF 160
-_SG.CF-,HT.P Heat Control Prop, Gain 0 - 1,5 1
-_SG.CF-,HT.D Heat Control Derv, Gain 0 - 1,5 1
-_SG.CF-,HT.TM Heat PID Rate Config 60 - 300 sec 90
SP SUPPLY STATIC PRESS,CFG,
-_SP.CF Static Pressure Config 0 - 1 (multi-text strings) No
-_SP.FN Static Pres,Fan Control? Yes Yes
-_SP.S Static Pressure Sensor Enable/Disable Disable
-_SP.LO Static Press, Low Range -10 - 0 0
-_SP.HI Static Press, High Range 0 - 10 5
-_SP.SP Static Pressure Setpoint 0 - 5 "H20 1,5
-_SP.MN VFD Minimum Speed 0 - 100 % 20
-_SP.MX VFD Maximum Speed 0 - 100 % 100
-_SP.FS VFD Fire Speed Override 0 - 100 % 100
-_SP.RS Stat, Pres, Reset Config 0 - 4 (multi-text strings) 0
-_SP.RT SP Reset Ratio ("/dF) 0 - 2,00 in, wg/dF 0,2
-_SP.LM SP Reset Limit in iwc (") 0 - 2,00 in, wg 0,75
-_SP.EC SP Reset Econo, Position 0 - 100 % 5
-_S.PID STAT.PR ESS,PID CONFIGS
-_S.PID-,SP.TM Stat,Pres,PID Run Rate 1 - 200 sec 2
-_S.PID-,SP.P Static Press, Prop, Gain 0 - 100 20
-_S.PID-,SP.I Static Pressure Intg, Gain 0 - 50 2
-_S.PID-,SP.D Static Pressure Derv, Gain 0 - 50 0
-_S.PID-,SP.SG Static Press,System Gain 0 - 50 1
ECON ECONOMIZER CONFIGURATION
-_EC.EN Economizer Installed? Yes/No Yes
-_EC.MN Economizer Min,Position 0 - 100 % 5
-_EC.MX Economizer Max,Position 0 - 100 % 98
-_E.TRM Economzr Trim For SumZ ? Yes/No Yes
-_E.SEL Econ ChangeOver Select 0 - 3 (multi-text strings) 1
-,OA.E.C OA Enthalpy ChgOvr Selct 1 - 5 (multi-text strings) 4
-,OA.EN Outdr, Enth Compare Value 18 - 28 24
-,OAT.L High OAT Lockout Temp -40 - 120 dF 60
-,O.DEW OA Dewpoint Temp Limit 50 - 62 dF 55
-,ORH.S Outside Air RH Sensor Enable/Disable Disable
-_E.TYP Economizer Control Type 1-3 (multi-text strings) 1
-_EC.SW Economizer Switch Config 0 - 2 (multi-text strings) 0
-_E.CFG ECON,OPERATION CONFIGS
-_E.CFG-,E.P.GN Economizer Prop,Gain 0,7 - 3,0 1
-_E.CFG-,E.RNG Economizer Range Adjust 0,5 - 5,0 ^F 2,5
-_E.CFG-,E.SPD Economizer Speed Adjust 0,1 - 10,0 0,75
-_E.CFG-,E.DBD Economizer Deadband 0,1 - 2,0 ^F 0,5
-,UEFC UNOCC,ECON,FREE COOLING
-,UEFC-,FC.CF Unoc Econ Free Cool Cfg 0-2 (multi-text strings) 0
-,UEFC-,FC.TM Unoc Econ Free Cool Time 0 - 720 min 120
-,UEFC-,FC.L.O Un,Ec,Free Cool OAT Lock 40 - 70 dF 50