49
FIOP MOISTUREMISER DEHUMIDIFICATION PACKAGE
STATIC PRESSURE DROP
(in. wg)
EVAPORATOR-FAN MOTOR EFFICIENCY
*Single phase/3 phase.
NOTE: Convert bhp to watts using the following formula:
UNIT SIZE
48HJ
UNIT NOMINAL
TONS
CFM PER TON
300 400 500
004
3 .04 .07 .09
005
4 .07 .12 .15
006
5 .09 .15 .21
007
6 .12 .20 .28
008
7
1
/
2
.08 .13 .18
009
8
1
/
2
.10 .15 .22
012
10 .08 .13 .18
014
12
1
/
2
.11 .18 .26
FIOP
Factory-Installed Option
UNIT SIZE
48HJ
EFFICIENCY%
004,005
75
006*
74/84
007
84
008,009
80
012
85
014
87
watts =
bhp (746)
motor efficiency
0.25
0.20
0.15
0.10
0.05
0.00
0
500
1000
1500 2000
FLOW (CFM)
STATIC PRESSURE (in. wg)
3 TO 6 TON
7 1/2 TO 12 1/2 TON
DURABLADE ECONOMIZER BAROMETRIC RELIEF
DAMPER CHARACTERISTICS — 48HJ004-007
DURABLADE ECONOMIZER BAROMETRIC RELIEF
DAMPER CHARACTERISTICS — 48HJ008-014
ECONOMI$ER BAROMETRIC RELIEF
DAMPER CHARACTERISTICS