HIGH-STATIC MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLET
LEGEND
*Used to determine minimum disconnect per NEC.
†Fuse or HACR circuit breaker per NEC.
**Units have 2 condenser-fan motors.
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR
breaker. The UL, Canada units may be fuse or circuit breaker.
2. Electrical data based on 95 F ambient outdoor-air temperature
± 10% voltage.
UNIT
NOMINAL
VOLTAGE
(V-Ph-Hz)
VOLTAGE
RANGE
COMPRESSOR
(each)
OFM IFM
COMBUSTION
FAN MOTOR
POWER
SUPPLY
MINIMUM UNIT
DISCONNECT
SIZE*
Min Max RLA LRA FLA FLA RLA MCA MOCP FLA LRA
48HJE,HJF004
208/230-3-60 187 254 10.3 77.0 0.7 5.8 0.6 25.4 30† 25 124
460-3-60 414 508 5.1 39.0 0.4 2.6 0.3 12.1 15† 12 63
575-3-60 518 632 4.2 31.0 0.4 2.6 0.3 9.8 15† 10 50
48HJD/HJE/HJF005
208/230-3-60 187 254 13.5 99.0 0.7 5.8 0.6 29.4 35† 29 146
460-3-60 414 508 7.4 49.5 0.4 2.6 0.3 15.0 20† 14 73
575-3-60 518 632 5.8 40.0 0.4 2.6 0.3 11.8 15† 11 59
48HJD/HJE/HJF006
208/230-3-60 187 254 17.3 123.0 1.5 7.5 0.6 36.6 40† 36 192
460-3-60 414 508 9.0 62.0 0.8 3.4 0.3 18.2 20† 18 96
575-3-60 518 632 7.1 50.0 0.8 3.4 0.3 14.4 20† 14 77
48HJE/HJF/HJD007
208/230-3-60 187 254 20.5 156.0 1.4 7.5 0.6 40.5 45† 39 224
460-3-60 414 508 9.6 70.0 0.6 3.4 0.3 18.7 25† 18 104
575-3-60 518 632 7.7 56.0 0.6 3.4 0.3 15.0 20† 15 89
48HJD/HJE/HJF008**
208/230-3-60 187 254 12.4 88.0 1.4 10.6 0.6 47.3 50† 49 267
460-3-60 414 508 6.4 44.0 0.7 4.8 0.3 23.3 25† 24 134
575-3-60 518 632 4.8 34.0 0.7 4.8 0.3 18.5 20† 19 95
48HJD/HJE/HJF009**
208/230-3-60 187 254 15.0 99.0 1.4 10.6 0.6 53.2 60† 55 264
460-3-60 414 508 8.2 49.5 0.7 4.8 0.3 27.4 30† 28 132
575-3-60 518 632 5.8 40.0 0.7 4.8 0.3 20.7 25† 21 107
48HJD/HJF/HJE012**
208/230-3-60 187 254 17.3 125.0 1.4 15.0 0.6 62.7 70 66 360
460-3-60 414 508 9.0 62.0 0.7 7.4 0.3 31.8 35† 32 181
575-3-60 518 632 7.1 50.0 0.7 7.4 0.3 25.9 30† 25 147
FLA —
Full Load Amps
HACR —
Heating, Air Conditioning and Refrigeration
IFM —
Indoor (Evaporator) Fan Motor
LRA —
Locked Rotor Amps
MCA —
Minimum Circuit Amps
MOCP —
Maximum Overcurrent Protection
NEC —
National Electrical Code
OFM —
Outdoor (Condenser) Fan Motor
RLA —
Rated Load Amps
UL —
Underwriters’ Laboratories
Electrical data (cont)