HIGH-STATIC MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLET
LEGEND
*Used to determine minimum disconnect per NEC.
Fuse or HACR circuit breaker per NEC.
**Units have 2 condenser-fan motors.
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR
breaker. The UL, Canada units may be fuse or circuit breaker.
2. Electrical data based on 95 F ambient outdoor-air temperature
± 10% voltage.
UNIT
NOMINAL
VOLTAGE
(V-Ph-Hz)
VOLTAGE
RANGE
COMPRESSOR
(each)
OFM IFM
COMBUSTION
FAN MOTOR
POWER
SUPPLY
MINIMUM UNIT
DISCONNECT
SIZE*
Min Max RLA LRA FLA FLA RLA MCA MOCP FLA LRA
48HJE,HJF004
208/230-3-60 187 254 10.3 77.0 0.7 5.8 0.6 25.4 30 25 124
460-3-60 414 508 5.1 39.0 0.4 2.6 0.3 12.1 15 12 63
575-3-60 518 632 4.2 31.0 0.4 2.6 0.3 9.8 15 10 50
48HJD/HJE/HJF005
208/230-3-60 187 254 13.5 99.0 0.7 5.8 0.6 29.4 35 29 146
460-3-60 414 508 7.4 49.5 0.4 2.6 0.3 15.0 20 14 73
575-3-60 518 632 5.8 40.0 0.4 2.6 0.3 11.8 15 11 59
48HJD/HJE/HJF006
208/230-3-60 187 254 17.3 123.0 1.5 7.5 0.6 36.6 40 36 192
460-3-60 414 508 9.0 62.0 0.8 3.4 0.3 18.2 20 18 96
575-3-60 518 632 7.1 50.0 0.8 3.4 0.3 14.4 20 14 77
48HJE/HJF/HJD007
208/230-3-60 187 254 20.5 156.0 1.4 7.5 0.6 40.5 45 39 224
460-3-60 414 508 9.6 70.0 0.6 3.4 0.3 18.7 25 18 104
575-3-60 518 632 7.7 56.0 0.6 3.4 0.3 15.0 20 15 89
48HJD/HJE/HJF008**
208/230-3-60 187 254 12.4 88.0 1.4 10.6 0.6 47.3 50 49 267
460-3-60 414 508 6.4 44.0 0.7 4.8 0.3 23.3 25 24 134
575-3-60 518 632 4.8 34.0 0.7 4.8 0.3 18.5 20 19 95
48HJD/HJE/HJF009**
208/230-3-60 187 254 15.0 99.0 1.4 10.6 0.6 53.2 60 55 264
460-3-60 414 508 8.2 49.5 0.7 4.8 0.3 27.4 30 28 132
575-3-60 518 632 5.8 40.0 0.7 4.8 0.3 20.7 25 21 107
48HJD/HJF/HJE012**
208/230-3-60 187 254 17.3 125.0 1.4 15.0 0.6 62.7 70 66 360
460-3-60 414 508 9.0 62.0 0.7 7.4 0.3 31.8 35 32 181
575-3-60 518 632 7.1 50.0 0.7 7.4 0.3 25.9 30 25 147
FLA
Full Load Amps
HACR
Heating, Air Conditioning and Refrigeration
IFM
Indoor (Evaporator) Fan Motor
LRA
Locked Rotor Amps
MCA
Minimum Circuit Amps
MOCP
Maximum Overcurrent Protection
NEC
National Electrical Code
OFM
Outdoor (Condenser) Fan Motor
RLA
Rated Load Amps
UL
Underwriters Laboratories
Electrical data (cont)