26
Outputs
Actuator signal: 2 --10 Vdc; minimum actuator impedance
is 2k ohm; bus two--wire output for bus communicating
actuators.
Exhaust fan, Y1, Y2 and AUX1 O:
All Relay Outputs (at 30 Vac):
Running: 1.5A maximum
Inrush: 7.5A ma ximum
Environmental
Operating Temperature: --40 to 150_F (--40 to 65_C).
Exception of display operation down to --4_F with full
recovery at --4_F from exposure to --40_F
Storage Temperature: --40 to 150_F (--40 to 65_C)
Shipping Temperature: --40 to 150_F (--40 t o 65_C)
Relative Humidity: 5% to 95% RH non--condensing
Economizer Module Wiring Details
Use Fig. 40 and Ta bles 3 and 4 to locate the wiring
terminals for the econom izer module.
NOTE: The four terminal blocks are removable . You can
slide out each terminal block, wire it, and then slide it
back into place.
W7220 Controller
Left Terminal
Block Label
Right Terminal
Block Label
NOTE: The bottom 4 Pin actuator header is not used
C14156
Fig. 40 -- W7220 Economizer Module Terminal
Connection Labels
S--Bus Sensor Wiring
The labels on the sensors and controller are color coded
for ease of installat ion. Orange labeled sensors can only
be wired to orange terminals on the controlle r. Brown
labeled sensors can only be wired to S --Bus (brown)
terminals. Use Fig. 41 and Table 5 to locate the wiring
terminals for each S --Bus sensor.
Use Fig. 41 and Table 6 to set the DIP switches for the
desired use of the sensor.
Table 3 Economizer Module --
Left Hand Terminal Blocks
Label Type Description
Top Left Termina l Block
MAT
MAT
20k NTC
and
COM
Supply Air Temperature Sensor
(polarity insensitive connection)
OAT
OAT
20k NTC
and
COM
Outdoor Air Temperature Sensor
(polarity insensitive connection)
S --- B U S
S --- B U S
S --- B u s
(Sylk* Bus)
Enthalpy Control Sensor
(polarity insensitive connection)
Bottom Left Terminal Block
I A Q 2 --- 1 0 2 --- 1 0 V d c Air Quality Sensor Input
(e.g. CO
2
sensor)
IAQ COM COM Air Quality Sensor Common
IAQ 24V 24 Vac Air Q uality Sensor 24 Vac Source
A C T 2 --- 1 0 2 --- 1 0 V d c Damper Actuator Output (2--- 10 Vdc)
ACT COM COM Damper Actuator Output Common
ACT 24V 24 V ac Damper Actuator 24 Vac Source
n/a The bottom pin is not used.
Table 4 Economizer Module --
Right Hand Terminal Blocks
Label Type Description
Top R ight Te rm in a l B loc k
n/a The first pin is not used
AUX2 I 24 Vac IN Shut Down (SD) or Heat (W)
Conventional only
or
Heat Pump Changeover (O/B) in
Heat Pump mode.
OCC 24 V ac IN Occupied / Unoccupied Input
E --- G N D E --- G N D Earth Ground --- System Required
EXH1 24 V ac OUT Exhaust Fan 1 Output
AUX1 O 24 Vac OUT Programmable:
Exhaust fan 2 output
or
Erv
or
System Alarm output
Bottom Right Terminal Block
Y 2 --- I 24 Vac IN Y2 in --- Cooling Stage 2 Input from
space thermostat
Y 2 --- O 24 V ac OUT Y2 out --- Cooling Stage 2 Output to
stage 2 mechanical cooling
Y 1 --- I 24 Vac IN Y1 in --- Cooling Stage 1 Input from
space thermostat
Y 1 --- O 24 V ac OUT Y1 out --- Cooling Stage 1 Output to
stage 1 mechanical cooling
C COM 24 Vac Common
R 24 V ac 24 Vac Power (Hot)
* Sylk is a trademark of Honeywell International Inc.