Table 7 -- Menu Structure* (cont)
Menu Parameter
Parameter
Default
Value
Parameter
Range and Increment
[
EXPANDED P ARAMET ER NAM E
Notes
SYSTEM
SETUP
INSTALL 01/01/10 Display ord er = MM /DD/YY
Setting order = DD, MM, then YY.
UNITS DEG _F _For_C Sets economi zer controller in degrees Fahrenheit or Celsius.
EQUIPMENT CONV Con ventional or HP CON V = conv e nt ional;
HP O/B = Enable Heat Pump mode. Use A UX2 I for Heat Pump i nput from
therm ostat or contro ller.
SeeMenuNote4
AUX2 IN n/a Shutdown (SD)
Heat (W1)
HP (O)
HP (B)
In CONV mode:
SD = Enables conf ig urati o n of shut d o w n (default ) ;
W = Informs controller that system is in heating mode.
NO T E : If usin g 2---speed fan mode, you mu s t prog r a m CONV mod e
forW.Shutdownisnotavailablein2---speedfanmode.
SeeMenuNote4.
In HP O/B mode:
HP(O) = energize heat pump on Cool (default);
HP(B) = energi ze heat pump on Heat.
FAN SPEED 1speed 1 speed/
2 speed
Sets economizer controller for operation of 1 speed or 2 speed supply fan.
The controller does not control the fan but posit i ons the OA and RA
dampers to the heating or cooling mode. See page 32 for modes and
position.
NO TE: 2--- speed fan opti on also needs Heat (W 1) programmed in
AUX 2 In. See Menu Note 4.
FAN CFM 5000cfm 100 to 15000 cfm;
increment by 100
UNI T DESIGN AI R FLOW (CFM)
Enter ONLY if using DCVCA L ENA = A UTO
The value is found the nameplate label for the specific RTU.
AUX1 OUT NONE NONE
ERV
EXH2
SYS
Select OUTPUT for AUX1 O relay
NONE = not configured (output is not used)
ERV = Energy Recovery Ventilator
[[
EXH2 = second damper position 24 Vac out for second exh a u st fan
SYS = use output as an alarm signal
OCC INPUT INPUT or ALW AYS OCCUPI ED MODE BY EXTERN A L SIGN AL
When usi ng a se t bac k therm ostat wit h occup a nc y out (2 4 Vac), the 24 Va c
is input “INPUT” to the OCC terminal. If no occupancy output from the
thermostat then change program to ALW AYS” OR add a jumper from
terminal R to OCC terminal.
SeeMenuNote1.
FACTORY DEFAULT NO NO or YES Resets all set points to factory defaults when set to YES. LCD will briefly
flas h YES and change to NO but all parame ters will change to the fac t o ry
de fault values.
NO T E : RECHECK AU X 2 IN a n d F A NT Y P E for requ i r ed 2--- speed
values.
ADV AN CED
SETUP
MA LO SET 45_F
(7_C)
35 to 65_F;
(2 to 18_C)
Incremented by 1_
SUPPL Y AIR TEMPERATURE LOW LIMIT
Temperature to activ ate Freeze Protecti on (clos e damper and alarm if
tem p e rature falls b elo w set up value)
FREEZE POS CLO CLO or MIN FREEZE PROTECTION DAMPER POSITION
Damper posi ti on when freeze protection is active
CLO = c los ed
MIN = MIN POS or VENTMAX
CO2 ZERO 0ppm 0 to 500 ppm:
Increment by 10
CO
2
ppm level to match CO
2
sensor start level.
CO2 SPAN 2000ppm 1000 to 3000 ppm;
Increment by 50
CO
2
ppm span to match CO
2
sensor. e.g.; 500---1500 sensor output would
be 500 CO
2
zero and 1000 CO
2
span.
STG3 DLY 2.0h 0 min, 5 min, 15 min,
then 15 min intervals.
Up to 4 h or OFF
COOLING STAGE 3 DELA Y
Delay after stage 2 for cool has been active. Turn s on second stage of
mechanical cooling when economizer is first stage call an d mechan ical
cooling is second stage call. Allows three stages of cooling, 1
economizer and 2 mechanical.
OFF = no Stage 3 cooling.
SD DMPR POS CLO CLO or OPN Ind ic at e s shut dow n signal from sp a c e thermo s t a t or unitary contro ller.
When controller receives 24 Vac input on the SD terminal in conventi onal
mode, the OA damper will open if programmed for OP N and OA damper
will cl o se if pro gr amme d f or C LO. Al l oth er c o ntr o ls, e.g. , Y1 --- O, Y2 --- O,
EXH1,etc.willshutoff.
NOTE: Function NOT AVAILABLE with 2--- speed mode
DA LO ALM 45_F
(7_C)
NONE
35 to 65_F; (2 to 18_C)
Incremented by 5_
UsedforalarmforwhentheDAairtemperatureistoolow.Setlowerrange
of alarm, below this temp erat ure the alarm will show on the disp lay.
DA HI ALM 80_F
(27_C)
NONE
70 to 180_F; (21 to 82_C)
Incremented by 5_
UsedforalarmforwhentheDAairtemperatureistoohigh.Sethighrange
of alarm, above this temperature the alarm will show on the di sp lay
DCVCAL ENA MAN MAN (manual)
AUTO
Turns on the DCV auto m at ic control of the dampers. Res e t s venti la t ion
based on t he RA, OA and MA sens o r conditions. Req uires all sens or s (RA,
OA, MA and CO
2
).
NOT E: Th is operat ion is not opera ble wit h a 2--- speed fa n unit.