Supply Air Temperature (SAT) Sensor
On FIOP--equipped 50HC unit, the unit is supplied with a
supply--air temperature (SAT) sensor (33ZCSENSAT).
This sensor is a tubular probe t ype, approx 6 inches (152
mm) in length. It is a nominal 10k ohm thermistor.
The SAT is factory--wired. The SAT probe is wire--tied to
the supply--air opening (on the horizontal opening end) in
its shipping position. Remove the sensor for installati on.
Re--position the sensor in the flange of the supply --air
opening or in the supply air duct (as required by local
codes). Drill or punch a
1
/
2
--in. hole in the flange or duct.
Use two field--supplied, self--drilling screws to secure the
sensor probe in a horizontal orie ntation. See Fig. 52.
SUPPLY AIR
RETURN AIR
SUPPLY AIR
TEMPERATURE
SENSOR
ROOF
CURB
C08200
Fig. 52 -- Typical Mounting Location for Supply Air
Temperature (SAT) Sensor on Small Rooftop Units
NOTE: Refer to the PremierL in k
t
Controller Ins ta llatio n,
Start--up, and Configuration Instructions for complete
PremierLink controller configuration, operating sequences
and troubleshooting information. Have a copy of this manual
available at unit start--up.
NOTE: The sensor must be mounted in the discharge
airstre am downstream of the cooli ng c oil and any heating
devic es. Be sure the probe tip does not come in contact
with any of the unit’s heater surfaces.
Outdoor Air Temperature (OAT) Sensor
The OAT is factory--mounted in the EconoMi$er
R
2(FIOP
or accessory). It is a nominal 10k ohm thermistor attached
to an eyelet mounting ring.
EconoMi$e r2
The PremierLink controller is used with EconoMi$er2
(option or accessory) for outdoor air m anagement. The
damper position is controlled directly by the PremierLink
controller; the EconoMi$er2 unit has no internal logic
devic e.
Outdoor a ir management functions can be enhance d with
field--installation of these accessory control devices:
Enthalpy control (outdoor air or differentia l sensors)
Space CO
2
sensor
Outdoor air CO
2
sensor
Refer to Table 18 for accessory part numbers.
Field Connections
Field connections for accessory sensor and input devices
are made at the 16--pole terminal block (TB1) located on
the control box bottom shelf in front of the PremierLink
controller (See Fig. 50 and 51). Some input devices also
require a 24--vac signal source; connect at CTB terminal
R at “THERMOSTAT” connection stri p for this signal
source. See connections figures on following pages for
field connection locati ons (and for continued connec tions
at the Premie rLink controller board inputs).
Table 19 provides a summary of field connections for units
equipped with Space Sensor. Table 20 provides a summary
of field connections for units equipped with Space
Thermostat.