5. Input wiring
Input wiring is common to all WTC types.
Each controller has physical connections for two
(2) inputs (marked as DIx for Digital Inputs on
X9connector)thatareconguredusinga
network tool or user interface (RCI-D).
All input wiring must be connected using the
provided detachable connectors.
Connectors allow the use of cables up to 1.5 mm².
Figure 1: X9 Digital input – Dry contact connection
External dry
contacts
(1) VREF
(2) COM
(3) DI2
(4) DI1
X9 wiring digital inputs (DI1, DI2)
Thisinputcongurationisusedtomonitor
digital dry contacts as, for instance, window
contact.
Power supply connections for all units
Power connection without Fuse Holder Power connection with the optional Fuse Holder