10. WTC LEDs operation
LONWORKS
BACNET
Order No.: 10083, 10.2016 - Supersedes order No.: 10083, 08.2015.
Rx/Tx LEDs (Rx – Receiving / Tx – Transmitting)
Rx LED not blinking Data is not being received from the LonWorks data bus.
Tx LED not blinking Data is not being transmitted onto the LonWorks data bus.
Status LED – Normal Operation
One fast blink
Initialization: The device is starting up.
Fast blink continuous
• • • • •
(150ms On, 150ms Off, continuous)
Firmware upgrade in progress. Controller operation is
temporarilyunavailable.Thenewrmwareisbeingloadedinto
memory. This takes a few seconds. Do not interrupt power to
the device during this time.
The Status LED is always ON The controller is operating normally.

Long Blink Continuous
(1s On, 1s Off, continuous)
Thecontrollerisnotcongured.
Action: Commission the controller.
Long Long Long blink
(800ms On, 300ms Off, 800ms On, 300ms
Off, 800ms On)
Thecontrollerisofine.
Action: Set the controller Online.
Long Short Short Short blink
• • •
(800ms On, 300ms Off, 150ms On, 300ms
Off, 150ms On, 300ms Off, 150ms On)
The controller is in bypass mode.
Action: Set the controller Online.
Fast blink 12x
• • • • • • • • • • • •
(80ms On, 80ms Off, 12x)
Wink. The wink function is used to identify a device.
Rx/Tx LEDs (Rx – Receiving / Tx – Transmitting)
Rx LED not blinking Data is not being received from the BACnet MS/TP data bus.
Tx LED not blinking Data is not being transmitted onto the BACnet MS/TP data bus.
Status LED – Normal Operation
One fast blink Initialization: The device is starting up.
Fast blink continuous:
• • • • •
(150ms On, 150ms Off, continuous)
Firmware upgrade in progress. Controller operation is
temporarilyunavailable.Thenewrmwareisbeingloadedinto
memory. This takes a few seconds. Do not interrupt power to
the device during this time.
The Status LED is always ON The controller is operating normally.

Long Long Long blink
(800ms On, 300ms Off, 800ms On,
300ms Off, 800ms On)
The device has not received a BACnet token, and therefore
cannot communicate on the network: Verify that the control-
ler’s MAC Address is unique on the BACnet MS/TP Data
Bus. Make sure the controller’s BAUD rate is the same as the
BACnet MS/TP Data Bus’ BAUD rate. Verify that the Max
Master is set high enough to include this controller’s MAC
Address (see also NCI documentation).
Short Long blink
(150ms On, 300ms Off)
Invalid MAC address: The device’s MAC address is set to
zero (0) or is set to an address higher than the Max Master
(see also NCI documentation).