6
EOL termination
Only the EOL termination of the last
subnetwork bus device is set to ON.
Setting the Subnet ID
Eachdeviceonthesubnetisidentiedwitha
subnet address. The Room Temperature
Sensor / Room Control Interface connected
to a controller’s Subnet Port must be set to a
unique subnet ID address. The address is by
default set to 1. Do not modify the
Subnet ID.
The address is set through the DIP switch
located next to the Subnet Port connectors.
Switch position Subnet ID
address
1 2 3 4 (EOL)
OFF OFF OFF ON or OFF 1
ON OFF OFF ON or OFF 1
OFF ON OFF ON or OFF 2
ON ON OFF ON or OFF 3
OFF OFF ON ON or OFF 4
English