20
Installation Procedures
Please refer to the attached manual for outdoor units.
Please refer to the attached manual for outdoor units.
Add the refrigerant according to the installation instruction for outdoor units. Compressor failure can be caused by lling
too much or too little refrigerant. Refer to the outdoor unit manual for additional evacuation and pressure test procedures
prior to system operation.
Proceed with the are tube connecting operation to connect all the refrigerant tubes.
• Dual wrenches must be used for connecting the indoor unit tubing.
For mounting torque, refer to the table on the right.
Cutting or enlarging pipes should be carried out by
installation personnel according to the operating
criterion, if the tube is too long or the are opening is
broken.
1. Connecting circular terminals:
The connecting method of the circular terminal is
shown in the Fig. Remove the screw, connect it to
the terminal tier after inserting it
through the ring
at the end of the lead and then
tighten it.
2. Connecting straight terminals:
The connection method for circular terminals is shown
in the Fig. Loosen the screw before inserting the line
terminal into the terminal tier, tighten the screw and
conrm that it has been clamped by pulling the line gently.
3. Pressing connecting line:
After line connection is completed, press the
connecting line with clips that should be pressed on the
protective sleeve of the connecting line.
Tubing permissible length and height dierence
Tubing materials and specications
Refrigerant lling quantity
Connecting procedures of refrigerant tubing
Cutting and enlarging Connecting
Model 40VU005C-009C -7S-QEE 40VU012C-018C -7S-QEE 40VU024R-054R -7E-QEE
Tubing Size (mm)
Gas pipe Ø9.52 Ø12.7 Ø15.88
Liquid pipe Ø6.35 Ø6.35 Ø9.52
Tubing Material Phosphor deoxy bronze seamless pipe (TP2) for air conditioner
Outer Diameter of
Tubing (mm)
Mounting Torque
(N-m)
Increase Mounting
Torque (N-m)
Ø6.35 11.8(1.2kgf-m) 13.7(1.4kgf-m)
Ø9.52 24.5(2.5kgf-m) 29.4(3.0kgf-m)
Ø12.7 49.0(5.0kgf-m) 53.9(5.5kgf-m)
wrench
Connecting
circular
terminals:
terminal tier
correct
pressing
wrong
pressing