Electrical Wiring
Indoor Units PCB
In the following table, 1 represents ON and 0 represents OFF. Denition principles of code switches:
SW01 is used to set the capabilities of the master and slave indoor units as well as the indoor unit; SW03 is used to set
the address of the indoor unit (combine original communication address and address of centralized controller).
(A) Denition and description of SW01
Dipswitch setting
English
[1] [2] [3] [4] Address of wire controlled indoor unit (group address)
0 0 0 0 0# (wire-controlled maer unit) (default)
SW01_1
0 0 0 1 1# (wire-controlled slave unit)
0 0 1 0 2# (wire-controlled slave unit)
SW01_2 Address of wire
0 0 1 1 3# (wire-controlled slave unit)
SW01_3 controlled indoor unit
0 1 0 0 4# (wire-controlled slave unit)
SW01_4
0 1 0 1 5# (wire-controlled slave unit)
∙∙∙ ∙∙∙ ∙∙∙ ∙∙∙ ∙∙∙
1 1 1 1 15# (wire-controlled slave unit)
[5] [6] [7] [8] Capability of indoor unit
SW01_5
0 0 0 0 40VU005C-7S-QEE
0 0 0 1 40VU007C-7S-QEE
SW01_6
SW01_7
Capability of indoor
unit
0 0 1 0 40VU009C-7S-QEE
0 0 1 1 40VU012C-7S-QEE
SW01_8
0 1 0 1 40VU016C-7S-QEE
0 1 1 0 40VU018C-7S-QEE