15
6.3 Pipe length and the elevation
The pipe length and refrigerant amount:
Capacity
Btu/h
Pipe size
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Additional
refrigerant
(g/m)
Gas Liquid
38KCD109313G+ 38KCD109313G
3/8’’
(Ф9.52)
1/4’’
(Ф6.35)
5 8 20 20
42KCD112313G+ 38KCD112313G
42KCD118313G + 38KCD118313G
1/2"
(Ф12.7)
1/4’’
(Ф6.35)
5 8 20 20
42KCD124313G+ 38KCD124313G
5/8’’
(Ф15.9)
3/8’’
(Ф9.52)
5 10 25 40
Caution:
The capacity test is based on the standard length and the maximum permissive length is based on the
system reliability.
The oil trap should be installed per 5-7 meters.