To address a ZS Sensor
Each ZS Sensor on an Rnet must have a unique address, but addresses do not have to be sequential.
Use the DIP switches on the back of the ZS Sensor to set an address from 0 to 14. (1 is factory default.) Each DIP
switch has the value shown in the figure below. Turn on as many DIP switches as you need so that their total value
equals the address.
DIP
Switch
value
1
ON
2
4
8
1 2 3 4
EXAMPLE DIP switches 1 and 4 above are on. Their values (1 + 8) total 9, so the sensor's address is 9.