Check for errors in the i-Vu® application and Snap.
On the control program's Properties page, select the Rnet Points tab. Verify that
values coming in from the sensors and those going out to the sensors are expected
values.
In the i-Vu® application, double-click the Sensor Binder and ASVI microblocks to
check for problems in the Status and/or Error columns.
If the Error column shows Resource Allocation, try formatting the sensor. If the error is
not corrected by formatting, the control program engineer should reduce the number
of items that the sensor is trying to display.
The sensor is not communicating with the network. Check:
• Software/addressing setup
• Wiring connections
• Controller operating status