Programming specific applications
ZS Sensor CARRIER CORPORATION ©2020
Applications Guide All rights reserved
23
5 Select
Show on
the
Information Screen
or
Diagnostics Screen
.
6 On the
Properties
tab in the
Rnet Text
fields, type the text that you want to a sensor to show for each fan
speed.
NOTES
The letters K, M, Q, W, X do not display on a screen.
If you do not enter text, the sensor will show the Value number for the fan speed.
When a user goes to the information screen, it will initially show the current fan speed. The user taps the
or
button to cycle through the fan speed options. The screen below shows High speed indicated by the icons and the
number 4 (no text was entered for that speed in the Property Editor).
Zone HVAC modes
A ZS Pro or ZS Pro-F sensor can:
Show heating or cooling status
Let the user manually run heating only, cooling only, or fan only
To show Heating and Cooling status
1 From the
Sys Out
microblock menu, add a
BACnet Multi-State Value Status
microblock.
2 On the Property Editor's
Rnet
tab, check
Enable Rnet
.
3 Select
Zone Mode Status (501)
from the
Rnet Tag
drop-down list.