ZS Sensors
Carrier Sensors CARRIER CORPORATION ©2021
Installation Guide All rights reserved
10
7 Insert the other 4 wires into the ZS Sensor's screw terminal connector. If wiring 2 cables, insert like-colored
wires into each terminal.
Carrier recommends that you use the
following Rnet wiring scheme:
Connect this
wire...
Red
Black
White
Green
To this
terminal...
+12V
Rnet-
Rnet+
Gnd
CAUTION Allow no more than 0.06 inch (1.5 mm) bare communication wire to protrude. If bare
communication wire contacts the cable's foil shield, shield wire, or a metal surface other than the terminal
block, the device may not communicate correctly.
8 Attach the sensor's cover and circuit board to the mounted backplate, inserting the top first.
9 Turn the setscrews one full turn counterclockwise so that the cover cannot be removed.
10 Turn on the controller's power.
NOTE Use the same polarity throughout the Rnet.