ZS Sensors
Carrier Sensors CARRIER CORPORATION ©2021
Installation Guide All rights reserved
13
To format a ZS Sensor
Formatting a sensor clears its flash memory. Do either of the following to format a sensor:
Download the controller that the sensor is connected to.
Do the following:
a) Remove the wiring connector from the sensor.
b) Note the current position of the DIP switches.
c) Set all DIP switches to the ON position.
d) Reattach the wiring connector to format.
e) After approximately 3 seconds, remove the wiring connector.
f) Set the DIP switches back to their original position.
g) Reattach the wiring connector.
NOTE If you move a sensor from one controller to another controller that has a different control program, format
the sensor.