Alternate space temperature sensor
Carrier Sensors CARRIER CORPORATION ©2021
Installation Guide All rights reserved
30
Field Service Options
Page
Description
126
Setpoint mode
00 = Use option page 103 setting
01 = Display single offset setpoint
02 = Display Heat/Cool setpoints
03 = Display Heat/Cool setpoints w/Occupied
(Occupied icon is shown in setpoint display mode.)
127
Setpoint feedback
00 = Disable feedback
01 = Enable Occupied/unoccupied feedback
02 = Enable Heat/Cool feedback
128
Maximum offset adjustment for setpoint
* Note: When using the -00° to +00° selection, option page 105 must be set to value 01.
* 00 = -00° to +00° (F or C)
01 = -01° to +01° (F or C)
02 = -02° to +02° (F or C) (Default)
03 = -03° to +03° (F or C)
04 = -04° to +04° (F or C)
05 = -05° to +05° (F or C)
06 = -06° to +06° (F or C)
07 = -07° to +07° (F or C)
08 = -08° to +08° (F or C)
09 = -09° to +09° (F or C)
10 = -10° to +10° (F or C)
129
Occupied heat setpoint
60 = Default (Range is 10 to 89)
130
Occupied cool setpoint
65 = Default (Range is 10 to 89)
131
Unoccupied heat setpoint
55 = Default (Range is 00 to 99)
132
Unoccupied cool setpoint
90 = Default (Range is 00 to 99)