Duct Air Temperature sensor
Carrier Sensors CARRIER CORPORATION ©2021
Installation Guide All rights reserved
34
Part #33ZCSENDAT
The Duct Air Temperature (DAT) sensor monitors supply air and is required for cooling and heating air source
applications on non-Carrier dampers and for stand-alone operation.
DAT sensor specifications
-40° to 245°F (-40° to 118°C) with a nominal resistance of 10,000 ohms at 77°F
(25°C). See table below.
Accuracy of ±0.36°F (0.2°C) from 0° to 70°C
Small, epoxy sensor, 1.25 inch (3.2 cm) long. Includes a mounting grommet and 75-
inch cable.
Thermistor Resistance vs. Temperature Values for Duct Temperature
Sensor
10K Type II (CP/MCI)
-40
-31
-22
-13
-4
5
14
23
32
41
50
59
68
77
86
95
104
113
122
131
140
149
158
-40
-35
-30
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
335,651
242,195
176,683
130,243
96,974
72,895
55,298
42,315
32,651
25,395
19.903
15,714
12,494
10,000
8,056
6,530
5,325
4,367
3,601
2,985
2,487
2,082
1,752