Duct Air Temperature sensor
Carrier Sensors CARRIER CORPORATION ©2021
Installation Guide All rights reserved
35
Wiring specifications
The sensor includes a 75-inch cable. To extend the length, use the cable specified below.
Cable from sensor to controller:
If <100 ft (30.5 meters) 22 AWG, unshielded
If >100 ft (30.5 meters) 22 AWG, shielded
Maximum length:
500 feet (152 meters)
Mounting location
Mount the sensor in the top or side of the supply duct.
Drill hole in top of duct
and let sensor hang down
Alternate location
inside of duct
Supply duct
To wire and mount the DAT sensor
1 Drill or punch a .25 inch (.6 cm) hole in the top or side of the supply duct.
2 Insert the sensor's probe into the hole. The probe can touch side of duct.
3 Snap the grommet into the hole until it is secure.
4 Pull on the sensor's wiring until the sensor is snug against the grommet.
5 Wire the sensor to the Open controller. See the controller's Installation and Startup Guide for details.