Relative Humidity sensors
Carrier Sensors CARRIER CORPORATION ©2021
Installation Guide All rights reserved
58
8 Wire the sensor to the Open controller. See diagrams below and the controller's Installation and Startup
Guide for details.
Input
Output
Wiring diagram
1836 Vdc
420 mA
1836 Vdc or
21.626.4 Vac
010 Vdc
9 Place the sensor's cover onto the probe unit and gently turn until it is tight.
10 Verify that you are getting a humidity reading.
NOTE Allow up to 20 minutes after powering up for the sensor reading to stabilize.