Relative Humidity sensors
Carrier Sensors CARRIER CORPORATION ©2021
Installation Guide All rights reserved
62
Transmitter outputs a 20 mA, 5 Vdc, or 10 Vdc signal regardless of
sensor reading. (For troubleshooting only.)
Shifts the RH output linearly up in 0.5% steps. Switch 4 must be set
to ON first. After switch 4 is ON, each time switch 5 if set to ON, the
RH output increases by 0.5%.
Shifts the RH output linearly down in 0.5% steps. Switch 4 must be
set to ON first. After switch 4 is ON, each time switch 6 if set to ON,
the RH output decreases by 0.5%.
Reset to
Original
Calibration
Resets the RH output back to the original calibration. Switch 4 must
be set to ON first. After switch 4 is ON, toggle switches 5 and 6 ON
then OFF. After 5 and 6 are OFF, slide switch 4 OFF.
RH conversion formulas
Use the following table to convert transmitter output signal to %RH.
Example:
If signal output is...
4-20 mA
4 mA = 0% RH
20 mA = 100% RH
0-10 Vdc
0 Vdc = 0% RH
10 Vdc = 100% RH
0-5 Vdc
0 Vdc = 0% RH
5 Vdc = 100% RH