Enthalpy switch/receiver and Enthalpy sensor
Carrier Sensors CARRIER CORPORATION ©2021
Installation Guide All rights reserved
64
Enthalpy switch/sensor specifications
The following specifications are the same for the switch/receiver and sensor unless noted.
-40° to 140°F (-40° to 60°C)
Operating relative humidity
0 to 100%, non-condensing
Sourced 24 Vac through 10 Amp Form 1C relay
2-wire, 4–20 mA loop powered
±0.36°F (0.2°C) from 32 to 158°F (0 to 70°C)
Relative humidity accuracy
Cable from sensor to controller:
If <100 ft (30.5 meters) 22 AWG, unshielded
If >100 ft (30.5 meters) 22 AWG, shielded
Mounting location
Mount the enthalpy switch/receiver in the outdoor air intake.
Mount the enthalpy sensor in the return air duct.
Do not mount the enthalpy switch/receivers and sensors where they could be exposed to outdoor elements such
as rain or snow. These units are not NEMA 4 enclosures.