Total Voltage Bias Percent (1058) – The percentage bias being applied to the voltage regulator
desired genset output voltage, as a percentage of 40% of rated, The value will increment by 0.5%
each time the Voltage Adjust up or down arrow is pressed on the EMCP 4 GSC, or any time the
Voltage Bias Percent Increment Command (1059) is written. The min/max values for this data are:
±
MAXIMUM_GENERATOR_VOLTAGE_OUTPUT_BIAS_PERCENTAGE_SETPOINT / 40%
Since the setpoint is limited to 0-100%, the absolute minimum and maximum are ± 250%.
Output voltage biasing is limited to ± 40% of rated, however, and voltage regulators may have an
even tighter range (the CDVR is ± 15%).
Voltage Bias Percent Increment Command (1059) – Increments the percentage bias to be
applied to the Automatic Voltage Regulator. This value gets added to the Total Voltage Bias
Percent register (the bias decreases if a negative value is written). The formula is:
T
OTAL_VOLTAGE_BIAS_PERCENT = TOTAL_VOLTAGE_BIAS_PERCENT + VOLTAGE_BIAS_PERCENT_INCREMENT_COMMAND
Voltage Compensation Bias Percent (1136) - Voltage bias as a percentage of nominal applied
based on Reactive Droop or Line Loss Compensation settings when configured for Integrated
Voltage Regulator.
Integrated Voltage Regulator Operating State (1137) - Indicates the operating state of the
Integrated Voltage Regulator feature when configured.
Generator Excitation Command Percentage (1138) - Reads the generator excitation command
percentage output from the Integrated Voltage Regulator feature (proportional to generator
excitation current).
FUEL TRANSFER MONITORING
Fuel Unload Pump Active (321) (EMCP 4.2 and 4.4 only) – status
Fuel Load Pump Active (322) – status
DEAD BUS ARBITRATION (EMCP 4.4 ONLY)
Arbitration Relay Active Status (DDO-01) (645)
Bus Live Status (1070)
Dead Bus Arbitration State (1111)
GENERATOR TO BUS SYNCHRONIZING (EMCP 4.4 ONLY)
Generator/Bus Phase Difference (1064)
Sync Mode Switch State (1108)
GENERATOR CIRCUIT BREAKER MONITORING AND CONTROL
Dedicated Digital Input #3 (Gen CB Aux A) Active Status (614)
Dedicated Digital Input #4 (Gen CB Aux B) Active Status (615)
Gen CB Trip Command Active Status (DIDI-03) (643)
Gen CB Close Command Active Status (DIDI-04) (644)
Gen CB Close Active Status (DDO-02) (646)
Gen CB Trip Active Status (DDO-03) (647)
Generator Circuit Breaker Status (1065)