Application and Installation Guide EMCP 4 SCADA Data Links
©2013 Caterpillar
All rights reserved. Page 51
ANALYSIS OF EVENT LOG DATA READ BY ABOVE PROCEDURE
First let’s look at the overall structure of the EMCP 4 response to the query for the first 8 log entries.
Now let’s look at an individual entry. Note from Appendix A, that each entry is 14 registers long; since
each register is 2 bytes long, each entry is 2 x 14 = 28 bytes long. So we can split up the data (let’s
consider only the data portion of the above response message) and deal with each log entry individually.
B0 10 09 01 3E 16 00 00 00 00 00 00 00 00 00 00 00 00 00 00 F5 09 FF 01 F4 FF
00 00
58 38 14 01 40 16 00 00 00 00 00 00 00 00 00 00 00 00 00 00 F4 0A FF 00 79 5F
00 01
B4 10 09 01 3E 16 00 00 00 00 00 00 00 00 00 00 00 00 00 00 F5 09 FF 00 17 C5
00 02
B8 10 09 01 3E 16 00 00 00 00 00 00 00 00 00 00 00 00 00 00 F5 09 FF 00 15 E3
00 03