Application and Installation Guide EMCP 4 SCADA Data Links
©2013 Caterpillar
All rights reserved. Page 54
Status is Present.
Bits 7:0 Occurrence Count = 00001001
Occurrence Count is 9.
Registers 12:11
= SPN/FMI: FF 01 F4 FF
Since these registers are also defined bitwise, we first convert the hex value to binary.
$FF 01 F4 FF = 1111 1111 0000 0001 1111 0100 111
1 1111
2
Bits 23:5 SPN = 0000 0001 1111 0100 111
2
= 4007
Bits 4:0 FMI = 1 1111
2
= 31
The SPN and FMI indicate the diagnostic trouble code. All of the trouble codes are listed in the
Diagnostic Trouble Code List in the EMCP Systems Operation Troubleshooting Testing and
Adjusting manual. From that manual, SPN 4007 FMI 31 indicates “Generator Control Not in
Automatic Warning”.
After decoding the first log entry, this event then translates to:
#1 Generator Control Not in Automatic Warnin
g
SPN 4007, FMI 31 Present, Occurrences: 9
last: Januar
y
16, 2007 09:16:44. 0 hrs
first: **** 0, 1985 00:00:00. 0 hrs
The translations for the other events in the above data are also given here for reference:
#2 Emer
g
enc
y
Sto
p
Switch Active
SPN 970, FMI 31 Active, Occurrences: 10
last: Januar
y
16, 2007 20:56:22. 0 hrs
first: **** 0, 1985 00:00:00. 0 hrs
#3 En
g
ine S
p
eed Sensor O
p
en
SPN 190, FMI 5 Present, Occurrences: 9
last: Januar
y
16, 2007 09:16:45. 0 hrs
first: **** 0, 1985 00:00:00. 0 hrs