CellarMate Manual Page 33
Humidity Too Low With Optional Humidifier
Possible Cause Solution
Humidifier not operating Check wiring for loose, broken, or frayed
connections
Check humidistat setup
Check for water flow & solenoid valve operation
Check damper operation
Humidifier operating Check for water being hot
Check drip pad—replace if scaled
Inadequate vapor barrier around cellar
Humidity Too High When Unit is Running, But Not Cooling
Possible Cause Solution
Compressor Check and reset high limit switch
Clear blockage of condenser air flow
Ambient temperature above 95°F
Humidity Too High When Unit is Not Running
Possible Cause Solution
Unit needs to run to
dehumidify
See Unit Not Operating section of the
Troubleshooting section
Humidity Too High When Unit is Running and Cooling
Possible Cause Solution
Too much evaporator air Add some resistance to air flow. Install a damper
in the ductwork.
Too much moisture in cellar Poor vapor barrier installation
Humidifier shutter is stuck open
Humidifier valve is stuck open
Humidifier is set too high