R410A DC Inverter Multi-split Technical Manual Outdoor Units
47
GD Chigo Heating & Ventilation Equipment Co., Ltd.
9.Electric Characteristics
Model
Outdoor Unit
Power Supply
OFM
Hz
Voltage
Min.
Max.
MCA
TOCA
MFA
kW
C2OU-14HVR1
50
220-240
198
254
5.7
7.4
30
0.06
C2OU-18HVR1
50
220-240
198
254
7.2
10.2
30
0.06
C3OU-21HVR1
50
220-240
198
264
8.9
11.8
30
0.06
C3OU-27HVR1
50
220-240
198
264
10.6
13.3
30
0.06
Remark:
MCA: Min. Current Amps. (A)
TOCA: Total Over-current Amps. (A)
MFA: Max. Fuse Amps. (A)
MSC: Max. starting Amps. (A)
RLA: Rated Locked Amps. (A)
OFM: Fan Motor.
FLA: Full Load Amps. (A)
KW: Rated Motor Output (kW)