99
Manual de Instrucciones
SVGm
ESPAÑOL
SVGm-3WF-300C-690
SVGm-4WF-201C-550
SVGm-3WF-400C-690
SVGm-4WF-268C-550
Tensión asignada de aislamiento Ui 690 V 690 V
Tensión soportada de impulso Uimp 6kV, CAT III Clase 1 6kV, CAT III Clase 1
Corriente asignada
SVGm-3WF-300C-690 SVGm-3WF-400C-690
252 A 336 A
SVGm-4WF-201C-550 SVGm-4WF-268C-550
210 A 280 A
Corriente de corta duración Icw 3.5 kA 1 segundo 3.5 kA 1 segundo
Corriente de cresta Ipk 84 kA pico 84 kA pico
Corriente de cortocircuito condicional Icc 40 kA 40 kA
Simultaneidad RDF 1 1
Consumo máximo
SVGm-3WF-300C-690 SVGm-3WF-400C-690
6600 W 8800 W
SVGm-4WF-201C-550 SVGm-4WF-268C-550
6000 W 8000 W
Corriente máxima
SVGm-3WF-300C-690 SVGm-3WF-400C-690
252 A RMS 336 A RMS
SVGm-4WF-201C-550 SVGm-4WF-268C-550
210 A RMS 280 A RMS
Potencia máxima
690V
SVGm-3WF-300C-690 SVGm-3WF-400C-690
300000 VA 400000 VA
550V
SVGm-4WF-201C-550 SVGm-4WF-268C-550
201000 VA 268000 VA
Medida de corriente
Tipo Transformador: 5/5A ... 5000/5A
Consumo 1.5 VA por transformador
Especificaciones del SVGm
Tiempo de respuesta < 100 s
Cos Φ programable 0.7 inductivo ... 1 ... 0.7 capacitivo
Paralelización
Hasta 100 unidades de diferente calibre
Conexión de los transformadores solo en unidad Master
Fusibles
SVGm-3WF-030M y SVGm-4WF-020M
Cantidad 2 por fase
Tipo BS88A1, 25A, 500Vac gG 80kA I
2
t 21kA
2
s
SVGm-3WF-060M y SVGm-4WF-040M
Cantidad 4 por fase
Tipo BS88A1, 25A, 500Vac gG 80kA I
2
t 21kA
2
s
SVGm-3WF-100M, SVGm-4WF-069M, SVGm-3WF-100R, SVGm-4WF-069R, SVGm-3WF-075M y SVGm-4WF-050M
Cantidad 2 por fase
Tipo tipo BS88 100A, 500Vac, gG 80kA I
2
t 21kA
2
s
SVGm-3WF-100C-690 y SVGm-4WF-067C-550
Cantidad 2 por fase
Tipo tipo BS88/A4 63A, 660/690Vac, gG 80kA I
2
t 23kA
2
s