Figure 16: Connecting Internal Ground and AC Power Connection for IW-6300H-AC-X-K9
Terminal block3Customer-supplied harness1
Customer-supplied cable (ATEX only)2
Step 4 Use a wire stripper tool to remove the insulation from each wire. Remove only enough wire to provide a solid
connection in the terminal block. The hot wires should have no bare wire exposed after the connection is
made.
Step 5 Insert the ground wire into the internal ground.
Step 6 Insert each hot wire into the AC entry terminal block.
Step 7 Use a Phillips screwdriver to tighten the terminal block set screws to secure the wires in the terminal block.
Step 8 Verify that no bare wire is exposed. If wire is exposed, remove it from the terminal block, adjust the length,
and reinstall.
Step 9 Check your work.
Step 10 Close the access point cover. See Closing the Access Cover, on page 14 for details.
Connecting DC Power to IW-6300H-DCW-x-K9
This product relies on the building’s installation for short-circuit (overcurrent) protection. Ensure that the
protective device is rated not greater than:10 A. Statement 1005
Warning
A readily accessible two-poled disconnect device must be incorporated in the fixed wiring. Statement 1022
Warning
Installing the Access Point
24
Installing the Access Point
Connecting DC Power to IW-6300H-DCW-x-K9