EasyManua.ls Logo

Cisco Nexus 7004 - Page 118

Cisco Nexus 7004
274 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 52: Inserting the Grounding Wire in the Grounding Lug
Grounding cable with 0.75 in. (19 mm) of insulation stripped from the end2NRTL listed 45-degree grounding lug1
Step 3 Use the crimping tool to crimp the lug to the grounding wire. Verify that the ground wire is securely attached to the
ground lug by attempting to pull the wire out of the crimped lug.
Step 4 Remove the adhesive label from one of the two system grounding pads, and secure the grounding wire lug to the grounding
pad with two M4 screws. Figure 53: Grounding Pad on the Cisco Nexus 7018 Chassis, on page 107 shows the location
of the grounding pad on the front side of the chassis. Ensure that the grounding lug and the grounding wire do not interfere
with other switch hardware or rack equipment.
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
106
Installing a Cisco Nexus 7018 Chassis
Connecting the System Ground