Fabric Module LEDs
StatusColorLED
All diagnostics pass. The module is operational (normal initialization sequence).GreenStatus
Indicates one of the following:
• The module is booting or running diagnostics (normal initialization
sequence).
• An over temperature condition has occurred (A minor temperature threshold
has been exceeded during environmental monitoring).
Orange
Indicates one of the following:
• The diagnostic test has failed. The module is not operational because a fault
has occurred during the initialization sequence.
• An over temperature condition has occurred. (A major temperature threshold
has been exceeded during environmental monitoring.)
Flashing Red
The module has detected a slot ID parity error and will not power on or boot up.Red
The fabric module is not receiving power.Off
The operator has has flagged this module for identification.
Flashing blueID
This module is not being identified.Off
Fan Tray LEDs
StatusColorLED
The fan tray is operational.GreenSTATUS
One or more fans is running below the threshold speed.
The fan tray is receiving insufficient power.
Flashing red
No power is going to the fan tray.Off
The operator has activated this LED to identify this module in the chassis.
Flashing blueID
This module is not being identified.Off
Cisco Nexus 7706 Hardware Installation Guide
OL-31330-01164
LEDs
Fabric Module LEDs