If available, you can use an uninterruptible power supply (UPS) to protect against power failures.
Avoid UPS types that use ferroresonant technology. These UPS types can become
unstable with systems such as the Cisco Nexus switches. These switches can have
substantial current draw fluctuations because of fluctuating data traffic patterns.
Caution
Ensure that circuits are sized according to local and national codes. For North America, the power
supply requires a 15-A or 20-A circuit.
To prevent loss of input power, ensure the total maximum loads on the circuits
supplying power to the switch are within the current ratings for the wiring and
breakers.
Caution
Statement 1076—Clearance Around the Ventilation Openings
To prevent airflow restriction, allow clearance around the ventilation openings
to be at least
Warning
• There is adequate clearance around the rack to install the switch and to allow for unimpeded airflow.
• You have the following equipment in addition to the switch and the kits shipped with the switch:
• Eight customer-supplied 12-24 or 10-32 screws (required for attaching slider rails and mounting
bracket to the mounting rails)
• Number 1 and number 2 Phillips screwdrivers with torque capability
• 3/16-inch flat-blade screwdriver
• Tape measure and level
• ESD wrist strap or other grounding device (wrist strap can be found in the accessory kit)
• Antistatic surface large enough to place the switch
• Grounding cable (6 AWG recommended), sized according to local and national installation
requirements; the required length depends on the proximity of the switch to proper grounding
facilities
• Crimping tool large enough to accommodate the girth of the grounding lug
• Wire stripping tool
Cisco Nexus 9408 NX-OS Mode Switch Hardware Installation Guide
12
Installing the Chassis
Preparing to Install the Chassis