Rotate the lever towards the front of the module.4Slide and hold the middle handle on the ejector lever
toward the end of the lever.
1
Make sure that the other end of the lever grabs the
front of the chassis to push the module onto the
connectors inside the slot.
5Fully rotate the release lever away from the front of
the module.
2
Slide the power supply into the open power supply
slot in the chassis until it stops with the front of the
module about 0.25 inches (0.6 cm) in front of the
chassis.
3
f) Rotate the ejector lever toward the front of the power supply and be sure that the other end of the lever locks into the
chassis.
The lever should click when you rotate it all the way to the front of the power supply. Be sure that the power supply
is fully inserted into the slot (the front of the power supply should be even with the surface of the chassis) and securely
in place.
g) Attach the power cable to the power receptacle on the power supply and rotate the power cable holder onto the plug
on the cable.
h) Make sure that the other end of the power cable is attached to the AC power source in one of the following ways:
If you are using the combined power mode or the n+1 redundancy mode, you must connect the power cable to
the same power source as used by the other power supplies in the same switch.
Cisco Nexus 9508 NX-OS Mode Switch Hardware Installation Guide
103
Replacing or Installing Modules, Fan Trays, and Power Supplies
Installing or Replacing a 3-kW AC Power Supply