RP208-30M3P-6-30
Table 10: Specifications for RP208-30M3P-6-30 PDU
DescriptionFeature
RP208-30M3P-6-30PID
North AmericaCountry
0URU size
66.5 x 2.05 x 2.1 in. (1689 x 52 x 53 mm)Dimensions (H x W x D)
VerticalMounting style
10 ft (3.04 m)Cable length
NEMA L15-30PPlug
8.64Maximum kW
200 to 240 VInput voltage
200 to 240 VOutput voltage
24 AAmperage
Three-phasePhase
50 to 60 HzFrequency
3 two-pole 20 ACircuit breakers
30 IEC 60320 C13 outlets with outlet grip
6 IEC 60320 C19 outlets with outlet grip
Outlets
RS-232Serial interface
10/100 EthernetEthernet interface
YesVoltage monitoring
32º to 140ºF (0º to 60ºC)Operating temperature
Figure 29: RP208-30M3P-6-30 PDU
Cisco R42612 Rack and RP-Series Metered Input PDU Installation Guide
55
Specifications
RP208-30M3P-6-30