REV. FEBRUARY 19th 2014
CLIMA-FLEX S.A. DE C.V.
4. ELECTRICAL DATA MODEL CLIV 230VAC/60 HZ/3PHASE
Unit Model
VOLT
PH
HZ
GAUGE
THW 75
°C
ELECTRICAL
PROTECTION (MCA1)
MOP
MCA
COMPRESSOR
FAN
MIN
MAX
LRA
OPERATING
AMPERAGE (1)
RLA
**
CANT.
RLA
HP
CLIV-ACC-036-A3S
220
3
60
8
20
13
19.70
12.90
73
7.50
12.9
1
2.77
1 1/4
CLIV-ACC-061-A3S
220
3
60
8
29
18
28.50
17.80
110
11.40
18.4
1
2.77
1 1/4
MCA
MAXIMUM CURRENT AMPACITY
MOP
MAXIMUM OPERATIONAL AMPACITY
LRA
LOCKED ROTOR AMPACITY
AMP OP
AMPACITY OF OPERATION
RLA
RATED LOAD AMPACITY
HP
HORSE POWER