DOMESTIC HOT WATER
DOMESTIC HOT WATER OPERATION
Information displayed:
storage temperature
2 - Automatic operation:
domestic hot water is produced automatically, according to the
requirement, using all the resources available.
3 - With thermal solar system only:
the storage tank temperature is ensured only using solar collectors,
even with a greater set point.
4 - With auxiliary heating only:
the storage tank temperature is maintained only using the auxiliary
heater (heater or integrated boiler).
5 - Deactivates the production:
excludes the production of domestic hot water.
In this mode, the temperature of the storage tank is not controlled.
6 - Boost:
Production of domestic hot water in the shortest time, in this way
the heat pump (and any electrical resistance) will work
simultaneously to reach the temperature set for domestic hot water
as quickly as possible.
select 1
select 7
DOMESTIC HOT WATER PROGRAMMING
Elfocontrol
3
EVO is equipped with 3 preset time schedules.
Up to 7 programs can be saved in the memory.
All programs can be modified.
select 12
DOMESTIC HOT WATER SETTINGS
8 - Water set point with heat pump
is indicated as RELOAD in the programming
9 - Water set point with heat pump
is indicated as MAINTENANCE in the programming
10 - Maximum temperature allowed with solar collector
11 - Minimum temperature difference to activate the solar collector: the
solar collector activates when the temperature is 5.0°C
higher than the storage tank
12 - Activates the circulation for 3 minutes every 30 minutes
The recirculation function prevents the stratification in the ACS
accumulation.
Is active only at the times foreseen by the scheduler (Maintenance
+ recirculation, Recharge + recirculation).
1
12
2
3
4
5
7
6
8
9
10
11
12