SYSTEM COMPONENT ADDRESSING
HID-TSMART THERMOSTATS
The indications given are valid for all versions of HID-TSmart
The thermostat is connected in daisy-chain topology (in-out) directly to the CONTROL4 NRG serial bus 485
Step Action
Picture
1 Alimentare il dispositivo
2
Press for more than 5 seconds at the bottom center where the context bar is
present
3 You access the CONFIGURATION menu
4 Select PARAMETERS menu
5 Scroll down to the Address parameter
6 Select the numeric value to the right of the parameter name
ADDRESSING PROCEDURE
HID-TSmart is supplied by default with Modbus address 150. Follow the procedure below to address the HID-TSmart if there is more than one
unit in the system.
HID-TSmart addressing
Unit
Modbus address
HID-TSmart 1 150
HID-TSmart 2 151
HID-TSmart 3 152
HID-TSmart 4 153
...
HID-TSmart 30 179