InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp – June 2013
14.2.1.12 Binary input: AccessLock int
This input forces the controller built-in terminal into monitoring mode.
Setpoints changes are disabled.
Using control buttons on the panel is disabled even if the controller is
in MAN mode.
Change of controller mode is disabled.
NOTE:
As the IS-NT and IGS-NT-BB do not have built-in terminal, this input is
assigned to the terminal or IntelliVision (display) #1, which is supposed to be
directly attached to the controller or mounted close to it.
14.2.1.13 Binary input: AccessLock D#2
This input forces the external local terminal or IntelliVision (display) #2 into
monitoring mode.
NOTE:
Local display means that it is connected to dedicated RS485. There is
possibility to connect up to 2 external displays in IG-NT-BB or 1 in IG-NT. It is
possible to connect up to 3 external displays in IS-NT-BB and in IS-NT.
Setpoints changes are disabled.
Using control buttons on the panel is disabled even if the controller is
in MAN mode.
Change of controller mode is disabled.
14.2.1.14 Binary input: AccessLock ext
This input forces all external remote terminals into monitoring mode.
Setpoints changes are disabled.
Executing commands is disabled.
Change of controller mode is disabled.
An external remote terminal is any device, which reads and/or writes data
from/into the controller and is connected to the controller via any other