InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp June 2013
294
15.2.1.11 Binary output: BusL fail
Relat
ed
FW
3.0
Desc
riptio
n
The output is open if healthy BusL voltage is present. It closes with a delay given by BusL
protections if BusL voltage or frequency gets out of the limits.
15.2.1.12 Binary output: BusR fail
Related FW
3.0
Description
The output is open if healthy busR voltage is present. It closes with a delay
given by busR protections if busR voltage or frequency gets out of the limits.
For example see BusL fail.