15 | Modbus Installation
Parameter
Name
Description
Modbus
Addr.
Type
Format
Range
Unit
W/R
Details
Status A
Operating status
unit A
31003
Input
Register
Integer
0-13
-
READ
0-Humidifying
1-Standby
2-Idle Drained
3-Keep Warm
4-Filling
5-Draining
6-Remote Off
7-Safety Loop
8-Warning
9-Fault
10-Blower Pack
11-Stopped
12-Partial Drained
13-Self Test
Service Status
B
Maintenance and
malfunctions
status unit B
31026
Input
Register
Integer
0-13
-
READ
0-Humidifying
1-Standby
2-Idle Drained
3-Keep Warm
4-Filling
5-Draining
6-Remote Off
7-Safety Loop
8-Warning
9-Fault
10-Blower Pack
11-Stopped
12-Partial Drained
13-Self Test
Main
Contactor A
Contactor unit A
31200
Input
Register
Integer
0 OR 1
-
READ
0 = Off
1 = On
Main
Contactor B
Contactor unit B
31201
Input
Register
Integer
0 OR 1
-
READ
0 = Off
1 = On
Inlet A
Inlet valve unit A
31202
Input
Register
Integer
0 OR 1
-
READ
0 = Off
1 = On
Inlet B
Inlet valve unit B
31203
Input
Register
Integer
0 OR 1
-
READ
0 = Off
1 = On
Drain A
Drain valve unit A
31204
Input
Register
Integer
0 OR 1
-
READ
0 = Off
1 = On
Drain B
Drain valve unit B
31205
Input
Register
Integer
0 OR 1
-
READ
0 = Off
1 = On