Modbus Installation | 18
The following points may be mapped for control:
Table 3: NH-EL Humidifier Modbus Parameters
Write RH or
Demand signal
value to control
channel 1 for
cylinder A
Requires Modbus or BACnet to
be enabled.
For most common
configurations, this is the
primary control signal
Write RH or
Demand signal
value to control
channel 2 for
cylinder A
Requires Modbus or BACnet to
be enabled.
Only applies to NH-EL-150 and
NH-EL-200 with cylinders in
independent operation mode
Write RH or
Demand signal
value to control
channel 1 for
cylinder B
Requires Modbus or BACnet to
be enabled.
Only applies to NH-EL-150 and
NH-EL-200 with dual channel
control enabled
Write RH or
Demand signal
value to control
channel 2 for
cylinder B
Requires Modbus or BACnet to
be enabled.
Only applies to NH-EL-150 and
NH-EL-200 with cylinders dual
channel control enabled and
cylinders in independent
operation mode
Sets a manual
capacity limit
restriction for
cylinder A
Limits output to percentage of
total cylinder capacity for
cylinder A (NH-EL-150 and NH-
EL-200 models only)
Sets a manual
capacity limit
restriction for
cylinder B (if
present)
Limits output to percentage of
total cylinder capacity for
cylinder B (NH-EL-150 and NH-
EL-200 models only)
BMS timeout
for Modbus and
BACnet
It is recommend to not change
the value from the factory
default (300)
Remotely
disable steam
production for
the unit
0 = Idle/Humidify
1 = Disable
Writes the
desired space
setpoint for
control channel
1 for cylinder A
Use only when sending RH
values to Dinput_A1.
For most common
configurations this is the
primary space setpoint
Writes the
desired space
setpoint for
control channel
2 for cylinder A
Use only when sending RH
value to Dinput_A2 with dual
channel control enabled
Writes the
desired space
setpoint for
control channel
1 for cylinder B
Use only with NH-EL-150 and
NH-EL-200 models when
sending RH value to
Dinput_B1 and cylinders are
in independent operation
mode
Writes the
desired space
setpoint for
control channel
2 for cylinder B
Use only with NH-EL-150 and
NH-EL-200 models when
sending RH value to
Dinput_B2 with dual channel
control enabled and cylinders
are in independent operation
mode