Modbus Installation | 20
Parameter
Name
Description
Modbus
Addr.
Type
Format
Range
Unit
R/W
Details
Humidifier_
Status_A
Reads the
status of the
unit for cylinder
A
30003
Input
Register
Integer
0 - 9
-
Read
0 = Humidifying
1 = Idle
2 = Idle Drain
3 = Keepwarm
4 = Filling
5 = Draining
6 = Disabled
7 = Safety Loop
8 = Warning
9 = Fault
Humidifier_
Status_B
Reads the
status of the
unit for cylinder
A
30026
Input
Register
Integer
0 - 9
-
Read
0 = Humidifying
1 = Idle
2 = Idle Drain
3 = Keepwarm
4 = Filling
5 = Draining
6 = Disabled
7 = Safety Loop
8 = Warning
9 = Fault
System_
Demand_A
Reads the
demand for
cylinder A
30006
Input
Register
Integer
0 100
%
Read
Demand Mode:
Summation of Input_A1 and
Input_A2
RH Mode:
PID calculation
System_
Demand_B
Reads the
demand for
cylinder A
30016
Input
Register
Integer
0 100
%
Read
Demand Mode:
Summation of Input_B1 and
Input_B2
RH Mode:
PID calculation
Safety_Loo
p_A
Reads the
status of the
safety loop for
cylinder A
30007
Input
Register
Integer
0 or 1
-
Read
0 = Open
1 = Closed
Safety_Loo
p_B
Reads the
status of the
safety loop for
cylinder B
30017
Input
Register
Integer
0 or 1
-
Read
0 = Open
1 = Closed
Run_Time_
A
Reads
operating time
for cylinder A
30010
Input
Register
Integer
0 -
5000
Hrs
Read
Displays the total time cylinder
A has been running since last
reset
Run_Time_
B
Reads
operating time
for cylinder B
30020
Input
Register
Integer
0 -
5000
Hrs
Read
Displays the total time cylinder
B has been running since last
reset
Weighted_
Hours_A
Reads the
weighted time
for cylinder A
30011
Input
Register
Integer
0 -
5000
Hrs
Read
An equated run time based on
Run_Time_A x
System_Demand_A
Weighted_
Hours_B
Reads the
weighted time
for cylinder B
30021
Input
Register
Integer
0 -
5000
Hrs
Read
An equated run time based on
Run_Time_A x
System_Demand_A